Main
Device short name
IDc
Device location in system
Group incomer
Range
Acti9
Earth-leakage protection class
Type AC
Neutral position
Left
Earth-leakage protection time delay
Instantaneous
Earth-leakage sensitivity
30 mA
Product Name
Acti9 IDc
[ui] rated insulation voltage
440 V AC 50/60 Hz
Complementary
9 mm pitches
4
[in] rated current
25 A
[ue] rated operational voltage
230 V AC 50/60 Hz conforming to IEC 60947-3
230 V AC 50/60 Hz conforming to IEC 61008-1
230 V AC 50/60 Hz conforming to IEC 61008-2-1
[ics] rated service breaking capacity
Idm = 1000 A
Control type
Toggle
Connection pitch
18 mm between phases
Handle front plate colour
85 mm
Product or component type
Residual current circuit breaker (RCCB)
tightening torque
2 N.m
[uimp] rated impulse withstand voltage
4 kV conforming to IEC 61008-1
Comb busbar and distribution block compatibility
Upside: Clario
Connections - terminals
Tunnel type terminals1…10 mm² flexible
Tunnel type terminals1…16 mm² rigid
Tunnel type terminals1…10 mm² flexible with ferrule
width (w)
36 mm
network frequency
50/60 Hz
Colour
White
Mounting mode
Fixed
Net weight
205 g
wire stripping length
13 mm
Embedding depth
76 mm
Mounting support
35 mm symmetrical DIN rail
depth
76 mm
Network type
AC
Pollution degree
3
residual current tripping technology
Electromechanical
Surge current
250 A
Rated conditional short-circuit current
Inc 6 kA
Poles description
2P
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
operating altitude
2000 m
ambient air temperature for operation
-5…70 °C
standards
IEC 61008-2-1
IEC 60947-3
IEC 61008-1
Tropicalisation
2 conforming to IEC 60947-3
2 conforming to IEC 61008-1
2 conforming to IEC 61008-2-1
relative humidity
95 % at 55 °C