Additional Information
curve
C
Main
Device short name
iDPN Vigi
Device location in system
Outgoer
Range
Clario
circuit breaker application
Distribution
Neutral position
Left
Number of protected poles
1
Earth-leakage protection time delay
Instantaneous
Earth-leakage sensitivity
300 mA
Product Name
IDPN Vigi
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
440 V AC conforming to EN 61009
Earthing system
TN-S
Complementary
9 mm pitches
4
product compatibility
Single terminal
[in] rated current
32 A at 30 °C
[ue] rated operational voltage
230 V AC 50 Hz between phase and neutral
[ics] rated service breaking capacity
4500 A at 230 V AC 50 Hz conforming to EN 61009
Control type
Toggle
Handle front plate colour
81 mm
Product or component type
Earth leakage circuit breaker
tightening torque
2 N.m
[uimp] rated impulse withstand voltage
4 kV conforming to EN 61009
Comb busbar and distribution block compatibility
Upstream: Clario
Connections - terminals
Cable (downstream) 0.75…16 mm² rigid
Cable (downstream) 0.33…10 mm² flexible
Cable (upstream) 0.75…16 mm² rigid
Cable (upstream) 0.33…10 mm² flexible
Contact position indication
Yes
width (w)
36 mm
network frequency
50 Hz
Colour
White
Local signalling
ON/OFF indication
Net weight
210 g
wire stripping length
13 mm
Earth-leakage protection
Integrated
Mounting support
DIN rail
depth
71 mm
mechanical durability
20000 cycles
electrical durability
10000 cycles conforming to EN 61009
magnetic trip limit
5...10 x In
Network type
AC
Pollution degree
3 conforming to EN 61009
Limitation class
3 conforming to EN 61009
residual current tripping technology
Voltage independent
Suitability for isolation
Yes
Poles description
1P + N
Environment
Ambient air temp for storage/transportation
-40…60 °C
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
2000 m
ambient air temperature for operation
-5…60 °C
standards
EN/IEC 61009-1
EN/IEC 61009-2-1
Tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C