Additional Information
curve
D
Main
Device short name
iDPN N
Range
Clario
Neutral position
Left
Number of protected poles
1
Product Name
IDPN
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
400 V AC 50/60 Hz conforming to IEC 60947-2
Complementary
9 mm pitches
2
[in] rated current
10 A
[ue] rated operational voltage
230 V AC 50/60 Hz between phase and neutral
[ics] rated service breaking capacity
6000 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Control type
Toggle
Handle front plate colour
81 mm
Product or component type
Miniature circuit-breaker
tightening torque
2 N.m
[uimp] rated impulse withstand voltage
4 kV conforming to IEC 60947-2
Connections - terminals
Tunnel type terminals downstream 0.33…10 mm² flexible
Tunnel type terminals downstream 0.75…16 mm² rigid
Tunnel type terminals upstream 0.33…10 mm² flexible
Tunnel type terminals upstream 0.75…16 mm² rigid
Locking options description
Padlocking device
Contact position indication
Yes
Device application
Distribution
width (w)
18 mm
network frequency
50/60 Hz
Colour
White
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Net weight
115 g
wire stripping length
13 mm
Earth-leakage protection
Separate block
Mounting support
DIN rail
depth
78 mm
mechanical durability
20000 cycles
electrical durability
20000 cycles
magnetic trip limit
10...14 x In
Network type
AC
Pollution degree
3 conforming to IEC 60947-1
Limitation class
3 conforming to EN/IEC 60898-1
Suitability for isolation
Yes
Poles description
1P + N
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
2000 m
Range of product
Clario
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60898-1
Tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C