Additional Information
curve
C
Main
Device short name
DPN N Vigi
Device location in system
Outgoer
Range
Acti9
circuit breaker application
Distribution
Neutral position
Left
Number of protected poles
1
Earth-leakage protection time delay
Instantaneous
Earth-leakage sensitivity
30 mA
Product Name
DPN Vigi
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
400 V AC conforming to EN 61009
Complementary
9 mm pitches
4
[in] rated current
25 A at 30 °C
[ue] rated operational voltage
230 V AC
[ics] rated service breaking capacity
6000 A at 230 V AC 50/60 Hz conforming to EN 61009
Control type
Toggle
Product or component type
Earth leakage circuit breaker
[uimp] rated impulse withstand voltage
4 kV conforming to EN 61009
Connections - terminals
Tunnel type terminals1 cable(s) 10 mm² flexible
Tunnel type terminals1 cable(s) 16 mm² rigid
Contact position indication
Yes
Colour
White
Local signalling
ON/OFF indication
Net weight
0.19 kg
Earth-leakage protection
Integrated
Mounting support
DIN rail
mechanical durability
20000 cycles
electrical durability
10000 cycles conforming to IEC 61009
magnetic trip limit
5...10 x In
Network type
AC
Pollution degree
3 conforming to EN 61009
Limitation class
3 conforming to EN 61009
residual current tripping technology
Voltage independent
Poles description
1P + N
Environment
Ambient air temp for storage/transportation
-40…60 °C
operating altitude
2000 m
ambient air temperature for operation
-5…60 °C
overvoltage category
III
standards
EN/IEC 61009-1
EN/IEC 61009-2-1
Tropicalisation
2 conforming to EN 61009
relative humidity
95 % at 55 °C