Additional Information
curve
D
Main
Device short name
C120H
Range
Acti9
Number of protected poles
1
Product Name
C120
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Complementary
9 mm pitches
3
[in] rated current
100 A at 30 °C
[ue] rated operational voltage
380...415 V AC 50/60 Hz
125 V DC
<= 144 V DC
12 V DC
220...240 V AC 50/60 Hz
230...400 V AC 50/60 Hz
130 V AC 50/60 Hz
12 V AC 50/60 Hz
[ics] rated service breaking capacity
15 kA 50 % conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz
7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
2.25 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
7500 A 50 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz
20 kA 100 % conforming to EN/IEC 60947-2 - 12 V DC
15 kA 100 % conforming to EN/IEC 60947-2 - <= 144 V DC
20 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
15 kA 50 % conforming to EN/IEC 60947-2 - 12 V AC 50/60 Hz
Control type
Toggle
Product certifications
EAC
Handle front plate colour
81 mm
Product or component type
Miniature circuit-breaker
tightening torque
3.5 N.m
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Comb busbar and distribution block compatibility
NO
Connections - terminals
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible
Contact position indication
Yes
Device application
Distribution
width (w)
27 mm
network frequency
50/60 Hz
Colour
White
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Net weight
0.205 kg
wire stripping length
15 mm
Earth-leakage protection
Without
Mounting support
35 mm symmetrical DIN rail
depth
73 mm
mechanical durability
20000 cycles
electrical durability
5000 cycles conforming to IEC 60947-2
magnetic trip limit
10...14 x In
Network type
AC
Pollution degree
3 conforming to IEC 60947-2
Limitation class
3 conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2
Poles description
1P
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
2000 m
Range of product
C120
ambient air temperature for operation
-30…60 °C
overvoltage category
IV
standards
EN/IEC 60898-1
EN/IEC 60947-2
Tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C