Main
Device short name
iPRD PV-DC
Signalling circuit voltage
AC: 250 V 50/60 Hz
Surge arrester type
Electrical distribution network
Product Name
Acti9 iPRD PV-DC
Complementary
9 mm pitches
6
[ue] rated operational voltage
1000 V +/- 10 % DC
[imax] maximum discharge current
40 kA
Product certifications
CE
response time
<= 25 ns
[in] nominal discharge current
15 kA
[uoc] open circuit voltage
833 V
Handle front plate colour
85 mm
Product or component type
Surge arrester with pluggable cartridge
tightening torque
3.5 N.m
[iscpv] short-circuit current rating
200 A
[ucpv] maximum continuous operating voltage
Differential mode: 1000 V L+/L-
Common mode: 1000 V L+/PE
Common mode: 1000 V L-/PE
Connections - terminals
Tunnel type terminal 2.5…25 mm² rigid
Tunnel type terminal 2.5…16 mm² flexible
Tunnel terminal 2.5…16 mm² flexible with ferrule
Output type
Contact (volt-free)
width (w)
54 mm
Colour
White (RAL 9003)
Ik degree of protection
IK03
Local signalling
White/red flag
Maximum [up] voltage protection level
Common mode <3.9 kV type 2 L+/PE
Common mode <3.9 kV type 2 L-/PE
Differential mode <3.9 kV type 2 L+/L-
Mounting mode
Clip-on
Net weight
400 g
Disconnector device type
Integrated disconnector
wire stripping length
14 mm
Mounting support
DIN rail
depth
69 mm
Signal contacts composition
1 SD (1 C/O)
Surge arrester class type
Type 2
Surge arrester technology
MOV
Signalling output current
0.25 A
Poles description
2P
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP40 on front face:
IP20 on terminal:
operating altitude
2000 m
Range of product
Acti9
ambient air temperature for operation
-25…60 °C
standards
EN 50539-11:2013
UTE C 61740-51
relative humidity
5…95 %