Main
Device short name
iPRD40
Surge arrester type
Electrical distribution network
Product Name
Acti9 iPRD
Remote signalling
Without
Earthing system
TN-C-S
Complementary
9 mm pitches
4
[uc] maximum continuous operating voltage
Common mode: 350 V L/PE
Common mode: 350 V N/PE
[ue] rated operational voltage
230/400 V AC (+/- 10 %) at 50/60 Hz
[imax] maximum discharge current
Common mode: 40 kA L/PE
Common mode: 40 kA N/PE
Product certifications
CE
[in] nominal discharge current
Common mode: 15 kA (L/PE)
Common mode: 15 kA (N/PE)
Handle front plate colour
85 mm
Product or component type
Surge arrester with pluggable cartridge
tightening torque
2.5 N.m
[ipe] ground residual current
0.003 mA
0.6 mA
[ut] temporary overvoltage
337 V L/N 5 s withstand
1200 V N/PE 200 ms safe failure mode
Connections - terminals
Tunnel type terminal (downside) 2.5…35 mm²
Tunnel type terminal (upside) 2.5…35 mm²
Device application
Distribution
width (w)
36 mm
Colour
White (RAL 9003)
Ik degree of protection
IK03 conforming to IEC 62262
Maximum [up] voltage protection level
Common mode <1.4 kV type 2 L/PE
Common mode <1.4 kV type 2 N/PE
Mounting mode
Clip-on (DIN rail)
Net weight
0.217 kg
Disconnector device type
Associated circuit breaker iC60H 50 A curve C - Icu 15 kA
Associated circuit breaker IC60N 40 A curve C - Icu 10 kA
Associated circuit breaker NG125H 63 A curve C - Icu 36 kA
Associated circuit breaker NG125L 63 A curve C - Icu 50 kA
Associated circuit breaker NG125N 40 A curve C - Icu 25 kA
Associated fuse gG 63 A - Icu 15 kA
Associated fuse gG 80 A - Icu 50 kA
depth
69 mm
Surge arrester class type
Type 2
Surge arrester technology
MOV
Poles description
2P
Environment
Ambient air temp for storage/transportation
-40…85 °C
operating altitude
2000 m
Range of product
Acti9
ambient air temperature for operation
-25…60 °C
standards
EN 61643-11:2012
IEC 61643-11:2011
quality labels
KEMA-KEUR
NF
relative humidity
5…95 %