Main
Device short name
iQuick PRD8r
Signalling circuit voltage
2 A/250 V AC 50/60 Hz
Surge arrester type
Electrical distribution network
Product Name
Acti9 iQuick PRD
Remote signalling
With
Earthing system
TN-C
IT 230
Complementary
9 mm pitches
12.7
[uc] maximum continuous operating voltage
Common mode: 350 V L/PE
[ue] rated operational voltage
230/400 V AC (+/- 10 %) at 50/60 Hz
[imax] maximum discharge current
Common mode: 8 kA L/PE
Product certifications
CE
[in] nominal discharge current
Common mode: 2 kA (L/PE)
Differential mode: 2 kA (L/N)
[uoc] open circuit voltage
10 kV type 3 common mode L/PE
Handle front plate colour
94 mm
Product or component type
Surge arrester with pluggable cartridge
tightening torque
2.5 N.m
Connections - terminals
Tunnel type terminal (downside) 2.5…25 mm²
Tunnel type terminal (upside) 2.5…25 mm²
Device application
Distribution
width (w)
113.6 mm
Colour
White (RAL 9003)
Ik degree of protection
IK05 conforming to IEC 62262
Maximum [up] voltage protection level
Common mode <1.4 kV type 3 L/PE
Common mode <1.2 kV type 2 L/PE
Mounting mode
Clip-on (DIN rail)
Net weight
0.67 kg
Disconnector device type
Integrated circuit breaker - Icu 25 kA
depth
75.9 mm
Signal contacts composition
1 SD (1 C/O)
Surge arrester class type
Type 2 + 3
Surge arrester technology
MOV
Poles description
3P
Environment
Ambient air temp for storage/transportation
-40…70 °C
operating altitude
2000 m
Range of product
Acti9
ambient air temperature for operation
-25…60 °C
standards
EN 61643-11:2012
IEC 61643-11:2011
quality labels
NF
KEMA-KEUR
relative humidity
5…90 %