Additional Information
curve
C
Main
Device short name
iK60N
Range
Acti9
Number of protected poles
4
Product Name
Acti9 iK60
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
440 V AC 50/60 Hz conforming to EN/IEC 60898-1
Complementary
9 mm pitches
8
[in] rated current
10 A at 30 °C
[ics] rated service breaking capacity
6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz
Control type
Toggle
Product certifications
SNI
Handle front plate colour
85 mm
Product or component type
Miniature circuit-breaker
tightening torque
2 N.m top or bottom
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60898-1
Connections - terminals
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible
Locking options description
Padlocking device
Contact position indication
No
Device application
Distribution
width (w)
72 mm
network frequency
50/60 Hz
Colour
White
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Net weight
400 g
wire stripping length
14 mm for top or bottom connection
Earth-leakage protection
Without
Mounting support
DIN rail
depth
78.5 mm
mechanical durability
20000 cycles
electrical durability
10000 cycles
magnetic trip limit
5...10 x In
Network type
AC
Pollution degree
2 conforming to EN/IEC 60898-1
Limitation class
3 conforming to EN/IEC 60898-1
Suitability for isolation
Yes conforming to EN/IEC 60898-1
Poles description
4P
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to IEC 60529
ambient air temperature for operation
-25…60 °C
overvoltage category
II
standards
EN/IEC 60898-1