Additional Information
curve
B
Main
Device short name
IC60N
Range
Acti9
Number of protected poles
3
Product Name
Acti9 iC60
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2
Complementary
9 mm pitches
6
[in] rated current
32 A
[ics] rated service breaking capacity
15 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 - 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 - 125...180 V DC
10 kA 100 % conforming to EN 60947-2 - 125...180 V DC
Control type
Toggle
Handle front plate colour
85 mm
Product or component type
Miniature circuit-breaker
tightening torque
3.5 N.m top or bottom
[uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2
Comb busbar and distribution block compatibility
Top or bottom: YES
Connections - terminals
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible
Contact position indication
Yes
Device application
Distribution
width (w)
54 mm
network frequency
50/60 Hz
Colour
White
Local signalling
Trip indicator
Mounting mode
Fixed
Net weight
0.375 kg
wire stripping length
14 mm for top or bottom connection
Earth-leakage protection
Separate block
Mounting support
DIN rail
depth
78.5 mm
mechanical durability
20000 cycles
electrical durability
10000 cycles
magnetic trip limit
4 x In +/- 20 %
Network type
AC
DC
Pollution degree
3 conforming to EN 60947-2
3 conforming to IEC 60947-2
Limitation class
3 conforming to EN 60898-1
3 conforming to IEC 60898-1
Suitability for isolation
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2
Poles description
3P
Utilisation category
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to IEC 60529
IP20 conforming to EN 60529
operating altitude
0...2000 m
ambient air temperature for operation
-35…70 °C
overvoltage category
IV
standards
IEC 60898-1
IEC 60947-2
EN 60898-1
EN 60947-2
Tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C