Additional Information
curve
C
Main
Device short name
iDPN N Vigi
Device location in system
Outgoer
Range
Acti9
Earth-leakage protection class
Type A
Neutral position
Left
Number of protected poles
1
Earth-leakage protection time delay
Instantaneous
Earth-leakage sensitivity
100 mA
Product Name
Acti9 iDPN Vigi
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
400 V AC 50 Hz
Complementary
9 mm pitches
4
[in] rated current
40 A
[ue] rated operational voltage
220...240 V AC 50 Hz
[ics] rated service breaking capacity
6000 A 100 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
Control type
Toggle
Product certifications
VDE
Connection pitch
9 mm between phase and neutral
Handle front plate colour
85 mm
Product or component type
Residual current breaker with overcurrent protection (RCBO)
tightening torque
2 N.m top or bottom
[uimp] rated impulse withstand voltage
4 kV
Comb busbar and distribution block compatibility
Top or bottom: YES
Connections - terminals
Single terminal top or bottom 1…16 mm² rigid
Single terminal top or bottom 1…10 mm² flexible
Single terminal top or bottom 1…10 mm² flexible with ferrule
Locking options description
Padlocking device
Contact position indication
Yes
Device application
Distribution
width (w)
36 mm
network frequency
50 Hz
Colour
White
Local signalling
ON, OFF, fault trip
Mounting mode
Clip-on
Net weight
125 g
wire stripping length
15 mm for top or bottom connection
Earth-leakage protection
Integrated
Mounting support
DIN rail
depth
73 mm
mechanical durability
20000 cycles
electrical durability
10000 cycles
magnetic trip limit
5...10 x In
Network type
AC
Pollution degree
3
Limitation class
3 conforming to EN/IEC 61009-2-1
residual current tripping technology
Voltage independent
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
1P + N
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
ambient air temperature for operation
-25…60 °C
electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1
overvoltage category
III conforming to IEC 60364
standards
EN/IEC 61009-2-1
Tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C