Main
Device short name
ARA iID
Signalling circuit voltage
Volt-free contact 24...230 V 0.01…1 A AC
[ui] rated insulation voltage
400 V
Complementary
9 mm pitches
7
product compatibility
2P iID
range compatibility
Acti 9 (Acti9 iID) residual current circuit breaker (RCCB)
Control type
Inhibition of automatism maintained 230 V AC 50/60 Hz
Ultimate reclosing impulse 230 V AC 50/60 Hz
Handle front plate colour
93 mm
Product or component type
Automatic recloser auxiliary
tightening torque
Power supply: 1 N.m
Input: 1 N.m
Output: 0.7 N.m
[uimp] rated impulse withstand voltage
6 kV
[us] rated supply voltage
230 V AC 50/60 Hz
Impulse duration
>= 200 ms control circuit
Comb busbar and distribution block compatibility
NO
input current
5 mA
width (w)
63 mm
Colour
White
Local signalling
Flashing orange LED: not operational
Flashing green LED: normal operation
Flashing red LED: reclosing cycle in progress
Fixed red LED: automatic recloser locked
Mounting mode
Fixed
Net weight
0.44 kg
wire stripping length
Power supply: 10 mm for bottom connection
Input: 10 mm for bottom connection
Output: 8 mm for top connection
Mounting support
DIN rail
depth
75.5 mm
electrical durability
5000 cycles
Pollution degree
3 conforming to IEC 60947
Signal contacts composition
2 OF volt-free contacts
Value of setting
Program 1: 1 reclosing attemp, short cycle
Program 2: 3 reclosing attemps, short cycle
Program 3: 5 reclosing attemps, long fixed cycle
Program 4: 5 reclosing attemps, long progressive cycle
Provision for padlocking
Padlockable
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 60529
ambient air temperature for operation
-25…60 °C
overvoltage category
II
Tropicalisation
2
relative humidity
93 % at 40 °C