Main
Device short name
ARA iC60
Signalling circuit voltage
24 V 10 mA AC/DC
230 V 1 A AC
[ui] rated insulation voltage
400 V
Complementary
9 mm pitches
7
product compatibility
2P iC60
1P + N iC60
1P iC60
range compatibility
Acti 9 (Acti9 iC60)
Control type
Inhibition of automatism maintained 230 V AC 50/60 Hz
Ultimate reclosing impulse 230 V AC 50/60 Hz
response time
< 500 ms
Handle front plate colour
93 mm
Product or component type
Automatic recloser auxiliary
tightening torque
Power supply: 1 N.m
Input: 1 N.m
Output: 0.7 N.m
[uimp] rated impulse withstand voltage
6 kV
[us] rated supply voltage
230 V AC 50/60 Hz
Impulse duration
>= 200 ms control circuit
Comb busbar and distribution block compatibility
NO
input current
5 mA
width (w)
63 mm
Colour
White
Local signalling
Flashing orange LED: not operational
Flashing green LED: normal operation
Flashing red LED: reclosing cycle in progress
Fixed red LED: automatic recloser locked
Mounting mode
Clip-on
Net weight
440 g
wire stripping length
Power supply: 10 mm for bottom connection
Input: 10 mm for bottom connection
Output: 8 mm for top connection
Mounting support
DIN rail
depth
75.5 mm
electrical durability
5000 cycles
Pollution degree
3 conforming to IEC 60947
Power consumption in w
2 W
Signal contacts composition
2 OF volt-free contacts
Value of setting
Program 1: 1 reclosing attemp, short cycle <10 s before reclosing /6 min check time
Program 2: 3 reclosing attemps, short cycle <10 s before reclosing /2 min check time
Program 2: 3 reclosing attemps, short cycle <1 min before reclosing /6 min check time
Program 2: 3 reclosing attemps, short cycle <3 min before reclosing /6 min check time
Program 3: 5 reclosing attemps, long fixed cycle <10 s before reclosing /2 min check time
Program 3: 5 reclosing attemps, long fixed cycle <1 min before reclosing /6 min check time
Program 3: 5 reclosing attemps, long fixed cycle <3 min before reclosing /6 min check time
Program 4: 5 reclosing attemps, long progressive cycle <10 s before reclosing /2 min check time
Program 4: 5 reclosing attemps, long progressive cycle <1 min before reclosing /6 min check time
Program 4: 5 reclosing attemps, long progressive cycle <3 min before reclosing /8 min check time
Program 4: 5 reclosing attemps, long progressive cycle <4 min before reclosing /10 min check time
Program 4: 5 reclosing attemps, long progressive cycle <5 min before reclosing /12 min check time
Provision for padlocking
Padlockable
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 60529
Range of product
Acti9
ambient air temperature for operation
-25…60 °C
overvoltage category
II
Tropicalisation
2
relative humidity
93 % at 40 °C