Main
Device short name
iCT
[uc] control circuit voltage
24 V AC 50 Hz
Product Name
Acti9 iCT
[ui] rated insulation voltage
500 V AC 50 Hz
poles
4P
Complementary
9 mm pitches
6
product compatibility
IACTs
IACTp
IACTc
IATEt
[ie] rated operational current
40 A AC-7A
15 A AC-7B
[ue] rated operational voltage
400 V AC 50 Hz
compatibility code
ICT
Control type
Remote and manual control
control signal type
Maintained
Handle front plate colour
85 mm
Product or component type
Contactor
tightening torque
Control circuit: 0.8 N.m
Power circuit: 3.5 N.m
[uimp] rated impulse withstand voltage
4 kV
Connections - terminals
Control circuit: tunnel type terminals2 cable(s) 1.5 mm² rigid
Control circuit: tunnel type terminals1 cable(s) 1.5…2.5 mm² rigid
Power circuit: tunnel type terminals1 cable(s) 6…16 mm² flexible
Power circuit: tunnel type terminals1 cable(s) 6…25 mm² rigid
Control circuit: tunnel type terminals2 cable(s) 1.5…2.5 mm² flexible
noise level
30 dB
Device application
Motor-heating-lighting
width (w)
54 mm
network frequency
50 Hz
switching frequency
100 switching operations/day
Colour
White
Local signalling
Action indicator
Mounting mode
Clip-on
Heat dissipation
2.1 W
maximum power
10.4 W at 400 V AC
Mounting support
35 mm symmetrical DIN rail
depth
60 mm
mechanical durability
1000000 cycles
electrical durability
100000 cycles IEC/EN 61095 40 A 50 Hz AC-7A
30000 cycles IEC/EN 61095 15 A 50 Hz AC-7B
30000 cycles IEC/EN 61095 50 Hz AC-7C
100000 cycles EN/IEC 60947-4-1 50 Hz AC-1
30000 cycles EN/IEC 60947-4-1 50 Hz AC-3
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b
Network type
AC
Pollution degree
2
Pole contact composition
4 NC
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20
operating altitude
2000 m
Range of product
Acti9
ambient air temperature for operation
-5…60 °C
standards
IEC/EN 61095
Tropicalisation
2 conforming to EN 60947-4-1
2 conforming to EN 61095
2 conforming to IEC 1095
relative humidity