Main
Control and monitoring type
Cascade
Device short name
CDS
number of channels
2
Product Name
Acti9 CDS
Complementary
9 mm pitches
10
[in] rated current
15 A for non-priority circuit
Adjustable from 5 to 90 A for priority circuit
[ue] rated operational voltage
230 V AC - 15...10 % at 50/60 Hz
Handle front plate colour
77 mm
Product or component type
Load-shedding contactor
tightening torque
Non-priority circuit: 2 N.m
Priority circuit: 3.5 N.m
Connections - terminals
Non-priority circuit: screw terminal2.5…10 mm² flexible
Non-priority circuit: screw terminal2.5…10 mm² rigid
Priority circuit: screw terminal10…35 mm² flexible
Priority circuit: screw terminal10…50 mm² rigid
width (w)
90 mm
Colour
White (RAL 9003)
Local signalling
Load-shedding indication: 2 LEDs (yellow)
Net weight
0.3 kg
setting
75
45
20
90
5
10
30
60
50
40
15
25
wire stripping length
12 mm
13 mm
Mounting support
35 mm symmetrical DIN rail
Wall mounted
Panel mounting
depth
60 mm
Power consumption in va
12 VA
Poles description
1P
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 60529
Range of product
Acti9
ambient air temperature for operation
-5…55 °C
standards
EN 50081-1
NF C 61-750
EN 50081-2
Tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C