All categories
Compare Cart

56171 - Residual current protection relay, Vigirex RH99M, 30 mA to 30 A, 48 VAC 50/60 Hz, DIN rail mounting - Schneider Electric

Expected in 2-4 weeks
56171 - Residual current protection relay, Vigirex RH99M, 30 mA to 30 A, 48 VAC 50/60 Hz, DIN rail mounting - Schneider Electric - Residual current protection relay, Vigirex RH99M, 30 mA to 30 A, 48 VAC 50/60 Hz, DIN rail mounting - Schneider Electric - 0
56171 - Residual current protection relay, Vigirex RH99M, 30 mA to 30 A, 48 VAC 50/60 Hz, DIN rail mounting - Schneider Electric
276,23 €
276,23 € incl. VAT
Text About:
Residual current protection relay, Vigirex RH99M, 30 mA to 30 A, 48 VAC 50/60 Hz, DIN rail mounting - Schneider Electric
276,23 €
SPECIFICATIONS
Main
Current sensors compatibility VigiPacT TOA earth leakage current sensor
VigiPacT A earth leakage current sensor
VigiPacT L earth leakage current sensor
Device short name RH99M
[ithe] thermal current under enclosure 8 A
Range VigiPacT
Earth-leakage protection class Type A
Earth-leakage sensitivity 0.03…30 A
Earth-leakage time delay Instantaneous for 0.03 A
Adjustable 9 settings 0…4.5 s for 0.03…30 A
Earthing system TT
IT
TN-S
Minimum load 10 mA at 12 V
Monitored distribution system 1000 V - AC at 50/60 Hz (maximum)
1000 V - AC at 400 Hz (maximum)
reset Manual reset
Relay application Protection relay
Residual earth-leakage sensitity adjustment type Adjustable 9 settings
Complementary
9 mm pitches 6
Handle front plate colour 81 mm
Product or component type Residual current protection relay
tightening torque Auxiliary power supply: 0.6 N.m top
Fault: 0.6 N.m bottom
Relay test and fault reset: 0.25 N.m bottom
Sensor: 0.25 N.m top
Voltage presence: 0.6 N.m bottom
[uimp] rated impulse withstand voltage 8 kV
[us] rated supply voltage 48 V AC 50/60 Hz 55...110 %
Connections - terminals Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12
Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Fault: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Fault: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12
Fault: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Relay test and fault reset: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16
Relay test and fault reset: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16
Relay test and fault reset: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16
Sensor: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16
Sensor: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16
Sensor: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16
Voltage presence: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
Voltage presence: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12
Voltage presence: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
type of measurement Earth fault current internal measurement, range: 80...100 %
Electrical shock protection class Class II
width (w) 54 mm
mechanical robustness Fire resistance conforming to IEC 60695-2-1
IK protection 2 joules: IK07 conforming to EN 50102
Vibrations 13.2...100 Hz: 0.7 g
Vibrations 2...13.2 Hz: +/- 1 mm
Ik degree of protection IK07 conforming to EN 50102
Net weight 0.3 kg
Monitoring Electronics (continuous)
Power supply (continuous)
Relay/sensor link (continuous)
wire stripping length Auxiliary power supply: 7 mm for top connection
Fault: 8 mm for bottom connection
Relay test and fault reset: 5 mm for bottom connection
Sensor: 5 mm for top connection
Voltage presence: 8 mm for bottom connection
Mounting support DIN rail
depth 74 mm
Pollution degree 3 conforming to IEC 60664-1
Power consumption in va 4 VA
type of setting Selector
Tamperproof of settings Protected by sealable cover
Test function Remote test
Local
Environment
Ambient air temp for storage/transportation -55…85 °C
ip degree of protection IP40 on front face: conforming to EN/IEC 60529
IP30 on side parts: conforming to EN/IEC 60529
IP20 on connection terminals: conforming to EN/IEC 60529
ambient air temperature for operation -35…70 °C
electromagnetic compatibility Conducted and radiated emissions: , B, conforming to CISPR 11
Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6
Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2
High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5
Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4
Radiated susceptibility: , 3, conforming to IEC 61000-4-3
overvoltage category IV
relative humidity 95 % at 55 °C
Recently viewed
276,23 €
276,23 € incl. VAT
Expected in 2-4 weeks