Main
Device short name
GA300
Range
VigiPacT
[ui] rated insulation voltage
1000 V
current sensor type
A type closed toroid
Complementary
[ie] rated operational current
630 A
range compatibility
VigiPacT RH10M residual current protection relay
VigiPacT RH10P residual current protection relay
VigiPacT RH21M residual current protection relay
VigiPacT RH21P residual current protection relay
VigiPacT RH68M residual current protection relay
VigiPacT RH86M residual current protection relay
VigiPacT RH86P residual current protection relay
VigiPacT RH99M residual current protection relay
VigiPacT RH99P residual current protection relay
VigiPacT RH197M residual current protection relay
VigiPacT RH197P residual current protection relay
VigiPacT RHU residual current protection relay
VigiPacT RHUs residual current protection relay
VigiPacT RMH residual current protection relay
[icw] rated short-time withstand current
85 kA for 0.5 s
Product certifications
CE
Handle front plate colour
360 mm
Product or component type
Earth leakage current sensor
[uimp] rated impulse withstand voltage
12 kV
Connections - terminals
Connection by clip 6.35 mm²
diameter
291 mm inner:
cable outer diameter
150 mm for 2 cables : 240 mm² (maximum)
Device application
Equipment monitoring and control
width (w)
390 mm
network frequency
45...440 Hz
Mounting mode
Fixed (cables)
Net weight
2.23 kg
depth
46 mm
Network type
AC/DC
Residual short-circuit withstand current
85 kA / 0.5 s conforming to IEC 60947-2
Pollution degree
Level 3 conforming to IEC 60664-1
Transformer ratio
1/1000
Environment
Ambient air temp for storage/transportation
-55…85 °C
ip degree of protection
Connectors: IP20
IP30
ambient air temperature for operation
-35…70 °C
Environmental characteristics
Exposure to damp heat not in service (25...55 °C, RH 95 %) : 28 cycles conforming to IEC 60068-2-30
Salt mist: Kb/2 conforming to IEC 60068-2-52
Exposure to damp heat in service: category C2: 48 hours conforming to IEC 60068-2-56
overvoltage category
IV
standards
IEC 60947-2