All categories
Compare Cart

33514 - Trip unit MicroLogic 7.0 A, ComPact NS630b to NS3200 fixed, selective and earthleakage protections - Schneider Electric

Expected in 2-4 weeks
33514 - Trip unit MicroLogic 7.0 A, ComPact NS630b to NS3200 fixed, selective and earthleakage protections - Schneider Electric - Trip unit MicroLogic 7.0 A, ComPact NS630b to NS3200 fixed, selective and earthleakage protections - Schneider Electric - 0
33514 - Trip unit MicroLogic 7.0 A, ComPact NS630b to NS3200 fixed, selective and earthleakage protections - Schneider Electric
1 630,42 €
1 630,42 € incl. VAT
Text About:
Trip unit MicroLogic 7.0 A, ComPact NS630b to NS3200 fixed, selective and earthleakage protections - Schneider Electric
1 630,42 €
SPECIFICATIONS
Main
Range ComPact
circuit breaker mounting mode Fixed
Protected poles description 3t
3t + N/2
4t
Earth-leakage sensitivity 10 A for class A
30 A for class AC
Trip unit name Micrologic 7.0 A
Trip unit technology Electronic
Trip unit rating 630 A at 50 °C
800 A at 50 °C
1000 A at 50 °C
1250 A at 50 °C
1600 A at 50 °C
2000 A at 50 °C
2500 A at 50 °C
3200 A at 50 °C
Trip unit protection functions Selective + earth-leakage protection
Complementary
[ii] instantaneous pick-up adjustment range Off
2...15 x In
[un] rated nominal voltage 60…800 ms
range compatibility ComPact NS1600b...3200
ComPact NS630b...1600
[ir] long-time protection pick-up adjustment range 0.4...1 x In
Product or component type Trip unit
[isd] short-time protection pick-up adjustment range 1.5...10 x Ir
[iδn] earth-leakage protection sensitivity adjustment range 0.5…30 A
[tr] long-time delay adjustment range 0.7…16.6 s at 7.2 x Ir
0.7…24 s at 6 x Ir
12.5…600 s at 1.5 x Ir
[tsd] short-time delay adjustment range 0…0.4 s I²t=off
0.1…0.4 s I²t=on
Device application Distribution
type of measurement Ammeter
Communication of data Measurement readout
Protection and alarm settings
network frequency 50/60 Hz
thermal memory 20 mn
Local signalling 3 LEDs (red) for electrical fault
1 LED (red) for internal error
long-time pick-up adjustment type ir (thermal protection) Adjustable 9 settings
long-time protection delay adjustment type tr Adjustable 9 settings
earth-leakage protection sensitity adjustment type iδn Adjustable 9 settings
Display type Digital display
Earth-leakage protection Integrated
earth-leakage protection time delay adjustement type δt Adjustable 5 settings
Network type AC
instantaneous protection pick-up adjustment type ii Adjustable 9 settings
short-time protection delay adjustment type tsd Adjustable
short-time protection pick-up adjustment type isd Adjustable 9 settings
Poles description 3P
4P
Protection type for overload protection (long time)
for short time short-circuit protection
for instantaneous short-circuit protection
for earth-leakage protection
Zone selective interlocking zsi With
Environment
Ambient air temp for storage/transportation -40…85 °C
Range of product ComPact NS630b...1600
ComPact NS1600b...3200
ambient air temperature for operation -25…70 °C
Recently viewed
1 630,42 €
1 630,42 € incl. VAT
Expected in 2-4 weeks