33473 - Circuit breaker ComPact NS1000H, 70 kA at 415 VAC, Micrologic 2.0 trip unit, 1000 A, fixed, 3 poles - Schneider Electric

Expected in 2-4 weeks
33473 - Circuit breaker ComPact NS1000H, 70 kA at 415 VAC, Micrologic 2.0 trip unit, 1000 A, fixed, 3 poles - Schneider Electric - Circuit breaker ComPact NS1000H, 70 kA at 415 VAC, Micrologic 2.0 trip unit, 1000 A, fixed, 3 poles - Schneider Electric - 0
33473 - Circuit breaker ComPact NS1000H, 70 kA at 415 VAC, Micrologic 2.0 trip unit, 1000 A, fixed, 3 poles - Schneider Electric
2 444,86 € -20%
2 444,86 € incl. VAT
3 056,08 €
Text About:
Circuit breaker ComPact NS1000H, 70 kA at 415 VAC, Micrologic 2.0 trip unit, 1000 A, fixed, 3 poles - Schneider Electric
2 444,86 € 3 056,08 €
SPECIFICATIONS
Main
Device short name Compact NS1000H
Range ComPact
circuit breaker mounting mode Fixed
Protected poles description 3D
Product Name ComPact NS
Trip unit name Micrologic 2.0
Trip unit technology Electronic
Trip unit rating 1000 A at 50 °C
[ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LI
performance level H 70 kA 415 V AC
Complementary
[ii] instantaneous pick-up adjustment range 1.5...10 x Ir
[in] rated current 1000 A at 50 °C
[ue] rated operational voltage 690 V AC 50/60 Hz
[ics] rated service breaking capacity 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[icw] rated short-time withstand current 19.2 kA 1 s conforming to IEC 60947-2
Control type Rotary handle
Toggle
depth (d) 147 mm
Product certifications ASTA
ASEFA
[ir] long-time protection pick-up adjustment range 0.4...1 x In
Connection pitch 70 mm
Handle front plate colour 327 mm
Product or component type Circuit breaker
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
Auxiliary contact composition 1 NO/NC
[tr] long-time delay adjustment range 12.5…600 s at 1.5 x Ir
0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir
Device application Distribution
width (w) 210 mm
network frequency 50/60 Hz
thermal memory 20 mn
Ik degree of protection IK07 conforming to EN 50102
Local signalling 4 LEDs (red) for fault indication
1 LED (yellow) for overload
power losses 22 W
long-time pick-up adjustment type ir (thermal protection) Adjustable 9 settings
Net weight 14 kg
long-time protection delay adjustment type tr Adjustable 9 settings
Downside connection Front
Earth-leakage protection Without
Mounting support Backplate
mechanical durability 10000 cycles
electrical durability 2000 cycles at 690 V In
4000 cycles at 690 V In/2
5000 cycles at 440 V In
6000 cycles at 440 V In/2
Network type AC
instantaneous protection pick-up adjustment type ii Adjustable
Pollution degree 3 conforming to IEC 60947
Suitability for isolation Yes conforming to EN/IEC 60947-2
Poles description 3P
Upside connection Front
Utilisation category Category B
Protection type L : for overload protection (long time)
I : for instantaneous short-circuit protection
Zone selective interlocking zsi Without
Environment
Ambient air temp for storage/transportation -50…85 °C
ip degree of protection IP40 conforming to IEC 60529
operating altitude 0...2000 m without derating
2000 m...5000 m with derating
Range of product ComPact NS630b...1600
ambient air temperature for operation -25…70 °C
standards EN/IEC 60947-2
relative humidity 0…95 %
Recently viewed
2 444,86 €
2 444,86 € incl. VAT
3 056,08 €
Expected in 2-4 weeks -20%