Main
Device short name
Compact NS1600N
Range
ComPact
Neutral position
Left
[ui] rated insulation voltage
1000 V AC 50/60 Hz conforming to IEC 60947-2
performance level
N 50 kA 415 V AC
Complementary
[in] rated current
1600 A at 50 °C
[ue] rated operational voltage
690 V AC 50/60 Hz
[ics] rated service breaking capacity
30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
[icw] rated short-time withstand current
19.2 kA 1 s conforming to IEC 60947-2
Control type
Motor mechanism with external connector
Motor mechanism
depth (d)
147 mm
Product certifications
ASEFA
LCIE
ASTA
Connection pitch
70 mm
Handle front plate colour
327 mm
Product or component type
Basic frame
[uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
Device application
Distribution
width (w)
280 mm
network frequency
50/60 Hz
Ik degree of protection
IK07 conforming to EN 50102
Mounting mode
Drawout
power losses
154 W
Integral instant protection
40 kA
Mounting support
Backplate
mechanical durability
10000 cycles conforming to IEC 60947-2
electrical durability
5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
1000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
2000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
2000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Network type
AC
Pollution degree
3 conforming to IEC 60947
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
4P
Utilisation category
Category B
Protection type
Without protection
Environment
Ambient air temp for storage/transportation
-50…85 °C
ip degree of protection
IP40 conforming to IEC 60529
Range of product
ComPact NS630b...1600
ambient air temperature for operation
-25…70 °C
standards
IEC 60947-2