Main
Device short name
Compact NS630bL
Range
ComPact
Neutral position
Left
[ui] rated insulation voltage
1000 V AC 50/60 Hz conforming to IEC 60947-2
performance level
L 150 kA 415 V AC
Complementary
[in] rated current
630 A at 50 °C
[ue] rated operational voltage
690 V AC 50/60 Hz
[ics] rated service breaking capacity
100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (electrical operation)
Control type
Motor mechanism
Motor mechanism with external connector
depth (d)
147 mm
Product certifications
LCIE
ASEFA
ASTA
Connection pitch
70 mm
Handle front plate colour
327 mm
Product or component type
Basic frame
[uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
Device application
Distribution
width (w)
280 mm
network frequency
50/60 Hz
Ik degree of protection
IK07 conforming to EN 50102
Mounting mode
Drawout
power losses
34 W
Mounting support
Backplate
mechanical durability
10000 cycles conforming to IEC 60947-2
electrical durability
2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
3000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
3000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
4000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Network type
AC
Pollution degree
3 conforming to IEC 60947
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
4P
Utilisation category
Category A
Protection type
Without protection
Environment
Ambient air temp for storage/transportation
-50…85 °C
ip degree of protection
IP40 conforming to IEC 60529
Range of product
ComPact NS630b...1600
ambient air temperature for operation
-25…70 °C
standards
IEC 60947-2