All categories
Compare Cart

33243 - Circuit breaker ComPact NS1000N, 50 kA at 415 VAC, Micrologic 2.0 A trip unit, 1000 A, fixed,3 poles - Schneider Electric

Expected in 2-4 weeks
33243 - Circuit breaker ComPact NS1000N, 50 kA at 415 VAC, Micrologic 2.0 A trip unit, 1000 A, fixed,3 poles - Schneider Electric - Circuit breaker ComPact NS1000N, 50 kA at 415 VAC, Micrologic 2.0 A trip unit, 1000 A, fixed,3 poles - Schneider Electric - 0
33243 - Circuit breaker ComPact NS1000N, 50 kA at 415 VAC, Micrologic 2.0 A trip unit, 1000 A, fixed,3 poles - Schneider Electric
3 081,59 €
3 081,59 € incl. VAT
Text About:
Circuit breaker ComPact NS1000N, 50 kA at 415 VAC, Micrologic 2.0 A trip unit, 1000 A, fixed,3 poles - Schneider Electric
3 081,59 €
SPECIFICATIONS
Main
Device short name Compact NS1000N
Range ComPact
circuit breaker mounting mode Fixed
Protected poles description 3D
Product Name ComPact NS
Trip unit name Micrologic 2.0 A
Trip unit technology Electronic
Trip unit rating 1000 A at 50 °C
[ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LI
performance level N 50 kA 415 V AC
Complementary
[ii] instantaneous pick-up adjustment range 1.5...10 x Ir
[in] rated current 1000 A at 50 °C
[ue] rated operational voltage 690 V AC 50/60 Hz
[ics] rated service breaking capacity 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
[icw] rated short-time withstand current 19.2 kA 1 s conforming to IEC 60947-2
Control type Rotary handle
Toggle
depth (d) 147 mm
Product certifications ASEFA
ASTA
[ir] long-time protection pick-up adjustment range 0.4...1 x In
Connection pitch 70 mm
Handle front plate colour 327 mm
Product or component type Circuit breaker
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
Auxiliary contact composition 1 NO/NC
[tr] long-time delay adjustment range 12.5…600 s at 1.5 x Ir
0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir
Device application Distribution
type of measurement Ammeter
width (w) 210 mm
network frequency 50/60 Hz
thermal memory 20 mn
Ik degree of protection IK07 conforming to EN 50102
Local signalling 4 LEDs (red) for fault indication
1 LED (yellow) for overload
power losses 22 W
long-time pick-up adjustment type ir (thermal protection) Adjustable 9 settings
Net weight 14 kg
long-time protection delay adjustment type tr Adjustable 9 settings
Downside connection Front
Display type LCD display
Earth-leakage protection Without
Mounting support Backplate
mechanical durability 10000 cycles
electrical durability 2000 cycles at 690 V In
4000 cycles at 690 V In/2
5000 cycles at 440 V In
6000 cycles at 440 V In/2
Network type AC
instantaneous protection pick-up adjustment type ii Adjustable
Pollution degree 3 conforming to IEC 60947
Suitability for isolation Yes conforming to EN/IEC 60947-2
Poles description 3P
Upside connection Front
Utilisation category Category B
Protection type L : for overload protection (long time)
I : for instantaneous short-circuit protection
Zone selective interlocking zsi Without
Environment
Ambient air temp for storage/transportation -40…85 °C
ip degree of protection IP40 conforming to IEC 60529
operating altitude 0...2000 m without derating
2000 m...5000 m with derating
Range of product ComPact NS630b...1600
ambient air temperature for operation -25…70 °C
standards EN/IEC 60947-2
relative humidity 0…95 %
Recently viewed
3 081,59 €
3 081,59 € incl. VAT
Expected in 2-4 weeks