Main
Device short name
Compact NS630bN
Range
ComPact
[ui] rated insulation voltage
800 V AC 50/60 Hz conforming to IEC 60947-2
performance level
N 50 kA 415 V AC
Complementary
[in] rated current
630 A at 50 °C
[ue] rated operational voltage
690 V AC 50/60 Hz
[ics] rated service breaking capacity
30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
[icw] rated short-time withstand current
19.2 kA 1 s conforming to IEC 60947-2
Control type
Rotary handle
Toggle
depth (d)
147 mm
Product certifications
LCIE
ASTA
ASEFA
Connection pitch
70 mm
Handle front plate colour
327 mm
Product or component type
Basic frame
[uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
Device application
Distribution
width (w)
210 mm
network frequency
50/60 Hz
Ik degree of protection
IK07 conforming to EN 50102
Mounting mode
Fixed
power losses
10 W
Integral instant protection
40 kA
Mounting support
Backplate
mechanical durability
10000 cycles conforming to IEC 60947-2
electrical durability
2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2
6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Network type
AC
Pollution degree
3 conforming to IEC 60947
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
3P
Utilisation category
Category B
Protection type
Without protection
Environment
Ambient air temp for storage/transportation
-50…85 °C
ip degree of protection
IP40 conforming to IEC 60529
Range of product
ComPact NS630b...1600
ambient air temperature for operation
-25…70 °C
standards
IEC 60947-2