Additional Information
2 conductors with the same cross-section awg flexible
16 ... 14 (converted acc. to IEC)
2 conductors with the same cross-section awg rigid
16 ... 14 (converted acc. to IEC)
rated cross section awg
2/0
Main
calorimetric heat release nfpa 130 (astm e 1354)
28 MJ/kg
catalog page
Page 192 (C-1-2019)
number of positions
1
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4046356813334
number of rows
1
Product type
High current terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
3213142
potentials
1
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
70 mm²
packing unit
10 pc
product key
BE1311
insulating material group
I
weight per piece (excluding packing)
125.2 g
weight per piece (including packing)
140.1 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
temperature index of insulation material (din en 60216-1 (vde 0304-21))
130 °C
Complementary
2 conductors with same cross section, flexible
1.5 mm² ... 2.5 mm²
maximum power dissipation for nominal condition
6.27 W
open side panel
No
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
1.5 mm² ... 2.5 mm²
height ns 32
85 mm
height ns 35/7,5
80 mm
number of connections
5
rated surge voltage
8 kV
2 conductors with same cross section, solid
1.5 mm² ... 2.5 mm²
conductor cross section, flexible [awg]
16 ... 6 (converted acc. to IEC)
Country of origin
CN
height ns 35/15
87.5 mm
length [l]
88.5 mm
conductor cross section, rigid [awg]
1.5 mm² ... 16 mm²
Handle front plate colour
79.4 mm
tightening torque
1.4 ... 1.5 Nm
conductor cross-section flexible (2 conductors with the same cross-section, with twin ferrule and plastic sleeve)
1.5 mm² ... 6 mm²
connection in acc. with standard
IEC 60947-7-1
cross section awg
16 ... 6 (converted acc. to IEC)
conductor cross section flexible, with ferrule without plastic sleeve
1.5 mm² ... 10 mm²
flexible conductor cross section (ferrule with plastic sleeve)
1.5 mm² ... 6 mm²
internal cylindrical gage
A5
number of connections per level
5
width (w)
20.3 mm
screw thread
M4
Colour
gray
stripping length
10 mm
Minimum order quantity
1 pc
nominal current
57 A
frequency
f1 = 5 Hz to f2 = 250 Hz
Maximum load current
192 A (in case of a 70 mm² conductor cross section, the maximum load current must not be exceeded by the total current of all connected conductors.)
Environment
acceleration
30g
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally friendly use period: unlimited = EFUP-e
Customs tariff number
85369010
degree of pollution
3
din rail/fixing support
NS 32/NS 35
eclass-11.0
27141120
requirement temperature-rise test
Increase in temperature ≤ 45 K
Specifications - Environmental Product Compliance:
No hazardous substances above threshold values
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
ETIM - 8
EC000897
overvoltage category
III
result
Test passed
revolutions
135
rotation speed
10 rpm
short-time withstand current 70 mm²
1.2 kA
test force setpoint
10 N
test voltage setpoint
2.2 kV AC
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400
asd level
6.12 (m/s²)²/Hz
time of exposure
30 s
pulse shape
Half-sine
shock duration
18 ms
specification
DIN EN 50155 (VDE 0115-200):2008-03
spectrum
Service life test category 2, bogie-mounted
test directions
X-, Y- and Z-axis (pos. and neg.)
test duration per axis
5 h