Additional Information
bridge data
48 A / 10 mm²
connection capacity awg
20 ... 8
connection capacity flexible
0.5 mm² ... 10 mm²
connection capacity rigid
0.5 mm² ... 16 mm²
identification
II 2 GD Ex eb IIC Gb
ex temperature increase
40 K (52.5 A / 10 mm²)
output
(Permanent)
for bridging with bridge
550 V
rated cross section awg
8
Main
calorimetric heat release nfpa 130 (astm e 1354)
28 MJ/kg
catalog page
Page 121 (C-1-2019)
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4046356494809
number of rows
1
Product type
Feed-through terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
3212123
potentials
1
Rated voltage
550 V
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
10 mm²
packing unit
50 pc
product key
BE2211
insulating material group
I
weight per piece (excluding packing)
26.16 g
weight per piece (including packing)
28.222 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
temperature index of insulation material (din en 60216-1 (vde 0304-21))
130 °C
Complementary
end cover width
2.2 mm
maximum power dissipation for nominal condition
1.82 W
open side panel
Yes
[in] rated current
52.5 A
height ns 35/7,5
50.5 mm
number of connections
2
rated surge voltage
8 kV
conductor cross section, flexible [awg]
20 ... 6 (converted acc. to IEC)
Country of origin
CN
height ns 35/15
58 mm
length [l]
67.7 mm
2 conductors with the same cross section, flexible, with twin ferrule with plastic sleeve
1.5 mm² ... 4 mm²
conductor cross section, rigid [awg]
1 mm² ... 16 mm²
Handle front plate colour
49.5 mm
connection in acc. with standard
IEC 60947-7-1
cross section awg
20 ... 6 (converted acc. to IEC)
Rated insulation voltage
500 V
conductor cross section flexible, with ferrule without plastic sleeve
4 mm² ... 10 mm²
flexible conductor cross section (ferrule with plastic sleeve)
2.5 mm² ... 10 mm²
nominal voltage
1000 V
internal cylindrical gage
A6
number of connections per level
2
width (w)
10.2 mm
Colour
blue
stripping length
18 mm ... 20 mm
Minimum order quantity
50 pc
nominal current
57 A
contact resistance
0.43 mΩ
frequency
f1 = 5 Hz to f2 = 150 Hz
Maximum load current
61.5 A
Environment
acceleration
5g
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally friendly use period: unlimited = EFUP-e
Customs tariff number
85369010
degree of pollution
3
din rail/fixing support
NS 35
eclass-11.0
27141120
requirement temperature-rise test
Increase in temperature ≤ 45 K
Specifications - Environmental Product Compliance:
No hazardous substances above threshold values
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
ETIM - 8
EC000897
overvoltage category
III
result
Test passed
revolutions
135
short-time withstand current 16 mm²
1.92 kA
operating temperature range
-60 °C ... 110 °C
rotation speed
10 rpm
short-time withstand current 10 mm²
1.2 kA
test force setpoint
5 N
test voltage setpoint
2.2 kV
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400
asd level
1.857 (m/s²)²/Hz
time of exposure
30 s
number of shocks per direction
3
pulse shape
Half-sine
shock duration
30 ms
specification
DIN EN 50155 (VDE 0115-200):2008-03
spectrum
Service life test category 1, class B, body mounted
temperature cycles
192
test directions
X-, Y- and Z-axis (pos. and neg.)
test duration per axis
5 h