Additional Information
general
The current is determined by the fuse used, the voltage by the light indicator.
Main
catalog page
Page 101 (C-1-2019)
number of positions
1
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4046356482516
number of rows
1
Product type
Fuse terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
3211861
potentials
1
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
4 mm²
packing unit
50 pc
product key
BE2234
insulating material group
I
weight per piece (excluding packing)
12.127 g
weight per piece (including packing)
13.037 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
Complementary
end cover width
2.2 mm
fuse
G / 5 x 20
maximum power dissipation for nominal condition
1.02 W
open side panel
Yes
height ns 35/7,5
64.8 mm
number of connections
2
rated surge voltage
6 kV
conductor cross section, flexible [awg]
24 ... 10 (converted acc. to IEC)
Country of origin
PL
height ns 35/15
72.3 mm
length [l]
56 mm
2 conductors with the same cross section, flexible, with twin ferrule with plastic sleeve
0.5 mm² ... 1 mm²
conductor cross section, rigid [awg]
0.5 mm² ... 6 mm²
Handle front plate colour
57.3 mm
conductor cross-section flexible (2 conductors with the same cross-section, with twin ferrule and plastic sleeve)
0.5 mm² ... 1 mm²
connection in acc. with standard
IEC 60947-7-3
cross section awg
24 ... 10 (converted acc. to IEC)
conductor cross section flexible, with ferrule without plastic sleeve
0.75 mm² ... 4 mm²
flexible conductor cross section (ferrule with plastic sleeve)
0.5 mm² ... 4 mm²
nominal voltage
500 V
internal cylindrical gage
A4
note
The current is determined by the fuse used, the voltage by the fuse or selected light indicator.
number of connections per level
2
width (w)
6.2 mm
Colour
black
Fuse type
Glass / ceramics / ...
stripping length
10 mm ... 12 mm
Minimum order quantity
1 pc
nominal current
6.3 A (the current is determined by the fuse used)
Maximum load current
6.3 A (with 6 mm² conductor cross section, rigid)
Environment
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally friendly use period: unlimited = EFUP-e
Customs tariff number
85369095
degree of pollution
3
eclass-11.0
27141116
requirement temperature-rise test
Increase in temperature ≤ 45 K
Specifications - Environmental Product Compliance:
No hazardous substances above threshold values
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
eclass-12.0
27141116
ETIM - 8
EC000899
overvoltage category
III
result
Test passed
revolutions
135
eclass-13.0
27250113
rotation speed
10 (+/- 2) rpm
test voltage setpoint
1.89 kV
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400
time of exposure
30 s
specification