Additional Information
- at bridging between non-adjacent terminal blocks
352 V
bridge data
19 A / 2.5 mm²
connection capacity awg
26 ... 14
- at cut-to-length bridging
220 V
connection capacity flexible
0.14 mm² ... 2.5 mm²
connection capacity rigid
0.14 mm² ... 4 mm²
identification
II 2 G Ex eb IIC Gb
ex temperature increase
40 K (19 A / 2.5 mm²)
output
(Permanent)
for bridging with bridge
550 V
rated cross section awg
14
Main
catalog page
Page 71 (C-1-2019)
number of positions
1
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4046356329798
number of rows
1
Product type
Feed-through terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
3209523
potentials
1
Rated voltage
550 V
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
2.5 mm²
packing unit
50 pc
product key
BE2211
insulating material group
I
weight per piece (excluding packing)
5.8 g
weight per piece (including packing)
6.4 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
Complementary
end cover width
2.2 mm
maximum power dissipation for nominal condition
0.77 W
open side panel
Yes
[in] rated current
19 A
height ns 35/7,5
36.5 mm
number of connections
2
rated surge voltage
8 kV
conductor cross section, flexible [awg]
26 ... 12 (converted acc. to IEC)
Country of origin
DE
height ns 35/15
44 mm
length [l]
48.5 mm
2 conductors with the same cross section, flexible, with twin ferrule with plastic sleeve
0.5 mm²
conductor cross section, rigid [awg]
0.34 mm² ... 4 mm²
Handle front plate colour
1.437 "
connection in acc. with standard
IEC 60947-7-1
cross section awg
26 ... 12 (converted acc. to IEC)
Rated insulation voltage
500 V
conductor cross section flexible, with ferrule without plastic sleeve
0.5 mm² ... 2.5 mm²
flexible conductor cross section (ferrule with plastic sleeve)
0.34 mm² ... 2.5 mm²
nominal voltage
800 V
internal cylindrical gage
A3
number of connections per level
2
width (w)
5.2 mm
Colour
blue
stripping length
8 mm ... 10 mm
Minimum order quantity
1 pc
nominal current
24 A (at 2.5 mm²)
contact resistance
0.93 mΩ
frequency
f1 = 5 Hz to f2 = 250 Hz
Maximum load current
23 A
Environment
acceleration
30g
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally friendly use period: unlimited = EFUP-e
Customs tariff number
85369010
degree of pollution
3
din rail/fixing support
NS 35
eclass-11.0
27141120
requirement temperature-rise test
Increase in temperature ≤ 45 K
Specifications - Environmental Product Compliance:
No hazardous substances above threshold values
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
ETIM - 8
EC000897
overvoltage category
III
result
Test passed
revolutions
135
operating temperature range
-60 °C ... 110 °C
rotation speed
10 rpm
short-time withstand current 2.5 mm²
0.3 kA
short-time withstand current 4 mm²
0.48 kA
test force setpoint
1 N
test voltage setpoint
2 kV
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400
asd level
6.12 (m/s²)²/Hz
time of exposure
30 s
number of shocks per direction
3
pulse shape
Half-sine
shock duration
18 ms
specification
DIN EN 50155 (VDE 0115-200):2008-03
spectrum
Service life test category 2, bogie-mounted
temperature cycles
192
test directions
X-, Y- and Z-axis (pos. and neg.)
test duration per axis
5 h