Main
Range
ComPact
Visible break
No
Product Name
ComPacT INS
[ui] rated insulation voltage
750 V AC 50/60 Hz
Complementary
[icm] rated short circuit making capacity
330 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz
50 kA switch-disconnector alone 690 V AC at 50/60 Hz
[ie] rated operational current
AC-22A: 630 A AC 50/60 Hz 220/240 V
AC-22A: 630 A AC 50/60 Hz 380/415 V
AC-22A: 630 A AC 50/60 Hz 440/480 V
AC-22A: 630 A AC 50/60 Hz 480 V NEMA
AC-22A: 630 A AC 50/60 Hz 500/525 V
AC-22A: 630 A AC 50/60 Hz 660/690 V
AC-23A: 630 A AC 50/60 Hz 220/240 V
AC-23A: 630 A AC 50/60 Hz 380/415 V
AC-23A: 630 A AC 50/60 Hz 440/480 V
AC-23A: 630 A AC 50/60 Hz 480 V NEMA
AC-23A: 630 A AC 50/60 Hz 500/525 V
AC-23A: 630 A AC 50/60 Hz 660/690 V
DC-22A: 550 A DC 125 V 2 poles in series
DC-23A: 550 A DC 125 V 2 poles in series
DC-23B: 630 A DC 125 V 2 poles in series
[ue] rated operational voltage
250 V DC
690 V AC 50/60 Hz
[icw] rated short-time withstand current
11.5 kA during 3 s conforming to IEC 60947-3
20 kA during 1 s conforming to IEC 60947-3
4 kA during 30 s conforming to IEC 60947-3
4.9 kA during 20 s conforming to IEC 60947-3
[ith] conventional thermal current
630 A at 60 °C
Control type
Red and yellow rotary handle
Handle colour
Red
Product certifications
KEMA-KEUR
CCC
Connection pitch
45 mm
Handle front plate colour
205 mm
Product or component type
Switch disconnector
[uimp] rated impulse withstand voltage
8 kV
8 kV conforming to IEC 60947-3
Contact position indication
Yes
width (w)
185 mm
network frequency
50/60 Hz
Ik degree of protection
IK07 conforming to EN 50102
Mounting mode
Fixed
maximum power
AC-23: 200 kW at 220/240 V AC 50/60 Hz
AC-23: 200 kW at 230 V AC 50/60 Hz (NEMA)
AC-23: 315 kW at 380/415 V AC 50/60 Hz
AC-23: 375 kW at 480 V AC 50/60 Hz (NEMA)
AC-23: 400 kW at 440 V AC 50/60 Hz
AC-23: 400 kW at 500/525 V AC 50/60 Hz
AC-23: 560 kW at 660/690 V AC 50/60 Hz
Net weight
4.6 kg
Downside connection
Front
Mounting support
Plate
Rail
depth
130 mm
mechanical durability
10000 cycles
electrical durability
AC-22A: 1500 cycles 440 V AC 50/60 Hz
AC-22A: 1500 cycles 500 V AC 50/60 Hz
AC-22A: 1500 cycles 690 V AC 50/60 Hz
AC-23A: 1500 cycles 440 V AC 50/60 Hz
AC-23A: 1500 cycles 500 V AC 50/60 Hz
AC-23A: 1500 cycles 690 V AC 50/60 Hz
DC-23A: 1000 cycles 125 V DC
DC-23B: 200 cycles 125 V DC
Network type
DC
AC
Pollution degree
3
Rated duty
Uninterrupted
Suitability for isolation
Yes
Poles description
3P
Upside connection
Front
Environment
Ambient air temp for storage/transportation
-50…85 °C
ip degree of protection
IP40 conforming to IEC 60529
ambient air temperature for operation
-25…70 °C
standards
IEC 60947-3
IEC 60947-1