SPECIFICATIONS
Main
Range ComPact
Visible break No
Product Name ComPacT INS
[ui] rated insulation voltage 750 V AC 50/60 Hz
Complementary
[icm] rated short circuit making capacity 30 kA switch-disconnector alone 690 V AC at 50/60 Hz
330 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz
[ie] rated operational current AC-22A: 200 A AC 50/60 Hz 220/240 V
AC-22A: 200 A AC 50/60 Hz 380/415 V
AC-22A: 200 A AC 50/60 Hz 440/480 V
AC-22A: 200 A AC 50/60 Hz 480 V NEMA
AC-22A: 200 A AC 50/60 Hz 500/525 V
AC-22A: 200 A AC 50/60 Hz 660/690 V
AC-23A: 200 A AC 50/60 Hz 220/240 V
AC-23A: 200 A AC 50/60 Hz 380/415 V
AC-23A: 200 A AC 50/60 Hz 440/480 V
AC-23A: 200 A AC 50/60 Hz 480 V NEMA
AC-23A: 200 A AC 50/60 Hz 500/525 V
AC-23A: 200 A AC 50/60 Hz 660/690 V
DC-22A: 200 A DC 125 V 2 poles in series
DC-22A: 200 A DC 250 V 4 poles in series
DC-23A: 200 A DC 125 V 2 poles in series
DC-23A: 200 A DC 250 V 4 poles in series
[ue] rated operational voltage 250 V DC
690 V AC 50/60 Hz
[icw] rated short-time withstand current 1.8 kA during 30 s conforming to IEC 60947-3
2.2 kA during 20 s conforming to IEC 60947-3
4.9 kA during 3 s conforming to IEC 60947-3
8.5 kA during 1 s conforming to IEC 60947-3
[ith] conventional thermal current 200 A at 60 °C
Control type Direct front rotary handle
Handle colour Black
Product certifications KEMA-KEUR
CCC
Connection pitch 35 mm
Handle front plate colour 136 mm
Product or component type Switch disconnector
Contact position indication Yes
width (w) 140 mm
network frequency 50/60 Hz
Ik degree of protection IK07 conforming to EN 50102
Mounting mode Fixed
maximum power AC-23: 110 kW at 440 V AC 50/60 Hz
AC-23: 110 kW at 480 V AC 50/60 Hz (NEMA)
AC-23: 132 kW at 500/525 V AC 50/60 Hz
AC-23: 160 kW at 660/690 V AC 50/60 Hz
AC-23: 55 kW at 220/240 V AC 50/60 Hz
AC-23: 55 kW at 230 V AC 50/60 Hz (NEMA)
AC-23: 90 kW at 380/415 V AC 50/60 Hz
Net weight 2.2 kg
Downside connection Front
Mounting support Rail
Plate
depth 96 mm
mechanical durability 15000 cycles
electrical durability AC-22A: 1500 cycles 440 V AC 50/60 Hz
AC-22A: 1500 cycles 500 V AC 50/60 Hz
AC-22A: 1500 cycles 690 V AC 50/60 Hz
AC-23A: 1500 cycles 440 V AC 50/60 Hz
AC-23A: 1500 cycles 500 V AC 50/60 Hz
AC-23A: 1500 cycles 690 V AC 50/60 Hz
DC-22A: 1500 cycles 250 V DC 4 poles in series
DC-23A: 1500 cycles 250 V DC 4 poles in series
Network type DC
AC
Pollution degree 3
Rated duty Uninterrupted
Suitability for isolation Yes
Poles description 4P
Upside connection Front
Environment
Ambient air temp for storage/transportation -50…85 °C
ip degree of protection IP40 conforming to IEC 60529
ambient air temperature for operation -25…70 °C
standards IEC 60947-3
IEC 60947-1