Main
calorimetric heat release nfpa 130 (astm e 1354)
28 MJ/kg
catalog page
Page 553 (C-1-2019)
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4017918099251
Mounting type
NS 15
number of rows
1
Product type
Micro terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
3100305
potentials
1
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
1.5 mm²
packing unit
50 pc
product key
BE1261
insulating material group
I
weight per piece (excluding packing)
2.283 g
weight per piece (including packing)
2.295 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
temperature index of insulation material (din en 60216-1 (vde 0304-21))
130 °C
Complementary
2 conductors with same cross section, flexible
0.14 mm² ... 0.5 mm²
end cover width
1 mm
maximum power dissipation for nominal condition
0.56 W
open side panel
Yes
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
0.25 mm² ... 0.34 mm²
number of connections
2
rated surge voltage
4 kV
2 conductors with same cross section, solid
0.14 mm² ... 0.5 mm²
conductor cross section, flexible [awg]
26 ... 16 (converted acc. to IEC)
Country of origin
TR
height ns 15
23.5 mm
length [l]
22 mm
conductor cross section, rigid [awg]
0.14 mm² ... 1.5 mm²
Handle front plate colour
0.925 "
tightening torque
0.22 ... 0.25 Nm
connection in acc. with standard
IEC 60947-7-1
cross section awg
26 ... 16 (converted acc. to IEC)
conductor cross section flexible, with ferrule without plastic sleeve
0.25 mm² ... 0.75 mm²
flexible conductor cross section (ferrule with plastic sleeve)
0.25 mm² ... 0.75 mm²
nominal voltage
400 V
internal cylindrical gage
A1
number of connections per level
2
width (w)
4.2 mm
screw thread
M2
Colour
gray
stripping length
6 mm
Minimum order quantity
1 pc
nominal current
17.5 A
Maximum load current
17.5 A (with 1.5 mm² conductor cross section)
Environment
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally friendly use period: unlimited = EFUP-e
Customs tariff number
85369010
degree of pollution
3
din rail/fixing support
NS 15
eclass-11.0
27141120
requirement temperature-rise test
Increase in temperature ≤ 45 K
Specifications - Environmental Product Compliance:
No hazardous substances above threshold values
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
ETIM - 8
EC000897
overvoltage category
III
result
Test passed
revolutions
135
rotation speed
10 rpm
short-time withstand current 1.5 mm²
0.18 kA
test force setpoint
1 N
test voltage setpoint
1.89 kV
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400
time of exposure
30 s