Main
calorimetric heat release nfpa 130 (astm e 1354)
28 MJ/kg
catalog page
Page 169 (C-1-2019)
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4046356701716
number of rows
1
Product type
Test disconnect terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
3047454
potentials
1
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
4 mm²
packing unit
50 pc
product key
BE1133
insulating material group
I
weight per piece (excluding packing)
15 g
weight per piece (including packing)
15.6 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
temperature index of insulation material (din en 60216-1 (vde 0304-21))
130 °C
Complementary
2 conductors with same cross section, flexible
0.14 mm² ... 1.5 mm²
assembly instructions
For isolation purposes, the screw head in NS 35/7,5 DIN rails may not exceed a height of 5 mm including the washer.
end cover width
2.2 mm
maximum power dissipation for nominal condition
1.02 W
open side panel
Yes
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
0.14 mm² ... 1.5 mm²
height ns 35/7,5
49.5 mm
number of connections
2
rated surge voltage
6 kV
2 conductors with same cross section, solid
0.14 mm² ... 1.5 mm²
conductor cross section, flexible [awg]
26 ... 10 (converted acc. to IEC)
Country of origin
PL
height ns 35/15
57 mm
length [l]
66 mm
2 conductors with the same cross section, flexible, with twin ferrule with plastic sleeve
0.5 mm² ... 2.5 mm²
conductor cross section, rigid [awg]
0.14 mm² ... 6 mm²
tightening torque
0.6 ... 0.8 Nm
connection in acc. with standard
IEC 60947-7-1
cross section awg
26 ... 10 (converted acc. to IEC)
conductor cross section flexible, with ferrule without plastic sleeve
0.14 mm² ... 4 mm²
flexible conductor cross section (ferrule with plastic sleeve)
0.14 mm² ... 4 mm²
nominal voltage
500 V
internal cylindrical gage
A4
number of connections per level
2
width (w)
6.2 mm
screw thread
M3
Colour
blue
stripping length
9 mm
Minimum order quantity
1 pc
nominal current
28 A
frequency
f1 = 5 Hz to f2 = 250 Hz
Maximum load current
28 A (bei 6 mm² Leiterquerschnitt starr)
Environment
acceleration
30g
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally Friendly Use Period = 50 years
Customs tariff number
85369010
eclass-11.0
27141126
requirement temperature-rise test
Increase in temperature ≤ 45 K
Specifications - Environmental Product Compliance:
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
eclass-12.0
27141126
ETIM - 8
EC000902
overvoltage category
III
reach svhc
Lead 7439-92-1
result
Test passed
revolutions
135
rotation speed
10 (+/- 2) rpm
short-time withstand current 4 mm²
3.2 kA
test voltage setpoint
1.89 kV
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400
asd level
6.12 (m/s²)²/Hz
time of exposure
30 s
number of shocks per direction
3
pulse shape
Semi-sinusoidal
shock duration
18 ms
specification
DIN EN 50155 (VDE 0115-200):2018-05
spectrum
Service life test category 2, bogie-mounted
test directions
X-, Y- and Z-axis (pos. and neg.)
test duration per axis
5 h