Additional Information
bridge data
130.5 A / 50 mm²
connection capacity awg
4 ... 1/0
2 conductors with same cross section, stranded
10 mm² ... 16 mm²
connection capacity flexible
25 mm² ... 50 mm²
2 conductors with the same cross-section awg flexible
8 ... 6
connection capacity rigid
16 mm² ... 50 mm²
2 conductors with the same cross-section awg rigid
8 ... 6
identification
II 2 GD Ex eb IIC Gb
ex temperature increase
40 K (133 A / 50 mm²)
output
(Permanent)
for bridging with bridge
690 V
rated cross section awg
1/0
torque range
6 Nm ... 8 Nm
Main
catalog page
Page 189 (C-1-2019)
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4017918091644
number of rows
1
Product type
High current terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
3009118
potentials
1
Rated voltage
690 V
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
50 mm²
packing unit
10 pc
product key
BE1311
insulating material group
I
weight per piece (excluding packing)
113.4 g
weight per piece (including packing)
120 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
Complementary
2 conductors with same cross section, flexible
10 mm² ... 16 mm²
maximum power dissipation for nominal condition
4.73 W
open side panel
No
[in] rated current
133 A
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
10 mm² ... 16 mm²
height ns 32
81 mm
number of connections
2
rated surge voltage
8 kV
2 conductors with same cross section, solid
10 mm² ... 16 mm²
conductor cross section, flexible [awg]
3 ... 2/0 (converted acc. to IEC)
Country of origin
IN
height ns 35/15
83.5 mm
length [l]
70.5 mm
conductor cross section, rigid [awg]
16 mm² ... 70 mm²
Handle front plate colour
3.287 "
tightening torque
6 ... 8 Nm
connection in acc. with standard
IEC 60947-7-1
cross section awg
6 ... 2/0 (converted acc. to IEC)
Rated insulation voltage
630 V
conductor cross section flexible, with ferrule without plastic sleeve
25 mm² ... 50 mm²
flexible conductor cross section (ferrule with plastic sleeve)
25 mm² ... 50 mm²
nominal voltage
1000 V
internal cylindrical gage
B10
note
Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
number of connections per level
2
width (w)
20 mm
screw thread
M6
Colour
gray
stripping length
24 mm
Minimum order quantity
1 pc
nominal current
150 A
contact resistance
0.1 mΩ
frequency
f1 = 5 Hz to f2 = 250 Hz
Maximum load current
133 A
Environment
acceleration
5g
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally friendly use period: unlimited = EFUP-e
Customs tariff number
85369010
degree of pollution
3
din rail/fixing support
NS 32/NS 35
eclass-11.0
27141120
requirement temperature-rise test
Increase in temperature ≤ 45 K
Specifications - Environmental Product Compliance:
No hazardous substances above threshold values
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
ETIM - 8
EC000897
overvoltage category
III
result
Test passed
revolutions
135
operating temperature range
-60 °C ... 110 °C
rotation speed
10 (+/- 2) rpm
short-time withstand current 50 mm²
6 kA
test force setpoint
10 N
test voltage setpoint
2.2 kV
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400
asd level
6.12 (m/s²)²/Hz
time of exposure
30 s
number of shocks per direction
3
pulse shape
Half-sine
shock duration
30 ms
specification
DIN EN 50155 (VDE 0115-200):2022-06
spectrum
Service life test category 2, bogie-mounted
test directions
X-, Y- and Z-axis (pos. and neg.)
test duration per axis
5 h