Additional Information
bridge data
116 A / 35 mm²
connection capacity awg
18 ... 2
2 conductors with same cross section, stranded
0.75 mm² ... 10 mm²
connection capacity flexible
0.75 mm² ... 35 mm²
2 conductors with the same cross-section awg flexible
18 ... 8
connection capacity rigid
0.75 mm² ... 50 mm²
2 conductors with the same cross-section awg rigid
18 ... 6
at bridging with insertion bridge
690 V
identification
II 2 GD Ex eb IIC Gb
ex temperature increase
40 K (130.5 A / 35 mm²)
output
(Permanent)
for bridging with bridge
690 V
rated cross section awg
2
torque range
3.2 Nm ... 3.7 Nm
list of bridges
Chain bridge / KBI- 15 / 0205203
Main
calorimetric heat release nfpa 130 (astm e 1354)
27,5 MJ/kg
catalog page
Page 213 (CL-2005)
flammability rating according to ul 94
V0
insulating material
PA
fire protection for rail vehicles (din en 45545-2) r22
HL 1 - HL 3
relative insulation material temperature index (elec., ul 746 b)
130 °C
fire protection for rail vehicles (din en 45545-2) r23
HL 1 - HL 3
gtin
4017918091552
number of rows
1
Product type
Feed-through terminal block
fire protection for rail vehicles (din en 45545-2) r24
HL 1 - HL 3
item number
3008012
potentials
1
Rated voltage
690 V
fire protection for rail vehicles (din en 45545-2) r26
HL 1 - HL 3
nominal cross section
35 mm²
packing unit
50 pc
product key
BE1211
insulating material group
I
weight per piece (excluding packing)
55.656 g
weight per piece (including packing)
57.6 g
smoke gas toxicity nfpa 130 (smp 800c)
passed
specific optical density of smoke nfpa 130 (astm e 662)
passed
static insulating material application in cold
-60 °C
surface flammability nfpa 130 (astm e 162)
passed
temperature index of insulation material (din en 60216-1 (vde 0304-21))
125 °C
Complementary
2 conductors with same cross section, flexible
0.75 mm² ... 10 mm²
maximum power dissipation for nominal condition
4.06 W
open side panel
No
[in] rated current
118.5 A
2 conductors with same cross section, flexible, with ferrule without plastic sleeve
0.75 mm² ... 10 mm²
height ns 32
67 mm
height ns 35/7,5
62 mm
number of connections
2
rated surge voltage
8 kV
2 conductors with same cross section, solid
0.75 mm² ... 16 mm²
conductor cross section, flexible [awg]
18 ... 2 (converted acc. to IEC)
Country of origin
DE
height ns 35/15
69.5 mm
length [l]
50 mm
2 conductors with the same cross section, flexible, with twin ferrule with plastic sleeve
0.75 mm² ... 6 mm²
conductor cross section, rigid [awg]
0.75 mm² ... 50 mm²
Handle front plate colour
2.441 "
tightening torque
3.2 ... 3.7 Nm
connection in acc. with standard
IEC 60947-7-1
cross section awg
18 ... 1/0 (converted acc. to IEC)
Rated insulation voltage
630 V
conductor cross section flexible, with ferrule without plastic sleeve
0.75 mm² ... 35 mm²
flexible conductor cross section (ferrule with plastic sleeve)
0.75 mm² ... 35 mm²
nominal voltage
1000 V
internal cylindrical gage
B9
number of connections per level
2
width (w)
15.1 mm
screw thread
M6
Colour
gray
stripping length
16 mm
Minimum order quantity
1 pc
nominal current
125 A
contact resistance
0.08 mΩ
Maximum load current
147 A
Environment
Ambient air temp for storage/transportation
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient air temperature for installation
-5 °C ... 70 °C
ambient temperature (actuation)
-5 °C ... 70 °C
china rohs
Environmentally friendly use period: unlimited = EFUP-e
Customs tariff number
85369010
degree of pollution
3
din rail/fixing support
NS 32/NS 35
eclass-11.0
27141120
requirement temperature-rise test
Increase in temperature ≤ 45 K
Specifications - Environmental Product Compliance:
No hazardous substances above threshold values
ambient air temperature for operation
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
ETIM - 8
EC000897
overvoltage category
III
result
Test passed
revolutions
135
operating temperature range
-60 °C ... 110 °C
rotation speed
10 rpm
short-time withstand current 35 mm²
4.2 kA
short-time withstand current 50 mm²
6 kA
test force setpoint
10 N
test voltage setpoint
2.2 kV
permissible humidity (storage/transport)
30 % ... 70 %
unspsc 21.0
39121400
time of exposure
30 s