Additional Information
Connecting capacity
Busbar 10 mm²
Rigid 25 ... 25 mm²
Flexible 25 ... 25 mm²
curve
C
Data sheet, technical information
2CSC423030B0201
Eclass
V11.0 : 27142207
Package level 1 depth / length
0.073 m
Operating characteristic
Instantaneous
Product net depth / length
0.069
m
Rohs status
Following EU Directive 2011/65/EU
Weee category
5. Small Equipment (No External Dimension More Than 50 cm)
Main
Number of protected poles
3
degree of protection
IP2X
sensitivity to earth leakage
300 mA
Complementary
Accessories available
Yes
Ambient air temperature
Operation -25...55 °C
Ccc certificate
2021980307001650
Cn8
85363030
Declaration of conformity - ce
9AKK106713A5597
Package level 1 gross weight
0.530 kg
Product net weight
0.480
kg
[in] rated current
25 A
Package level 1 height
0.096 m
Product net width
0.071
m
Country of origin
Italy (IT)
Package level 1 units
box 1 piece
Package level 1 width
0.076 m
Environmental information
refer to RoHS information
Instructions and manuals
9AKK106713A8790
mechanical endurance
20000 cycle
Position of neutral terminals
Right
Minimum order quantity
1 piece
Options provided
None
Input voltage type
AC
Power supply connection
Arbitrary
Object classification code
F
Rated conditional short-circuit current (inc)
10 kA
frequency
50/60 Hz
Network type
AC type
Package level 1 ean
8012542517825
Rated cross-section
4 - Multi-Wired 1...25 mm²
1 - Solid-Core 25...25 mm²
Pollution degree
2
Product net height
0.085
m
Rated short-circuit capacity
(230 / 400 V AC) 6 kA
Rated frequency (f)
50 … 60 Hz
Rated impulse withstand voltage (uimp)
4 kV
Rated insulation voltage (ui)
500 V
Rated service short-circuit breaking capacity, in % of icu (ics)
6 kA
Rated voltage (ur)
400-415 V AC
Power loss
10.3 W
Rated operational voltage
400 … 415 V AC
Reach declaration
9AKK108467A9482
Poles description
4
Rated ultimate short-circuit breaking capacity (icu)
10 kA
Environment
Built-in depth (t2)
69 mm
Customs tariff number
85363030
Electrical endurance
10000 cycle
Energy limiting class
3
Release type
C
ETIM - 8
EC000905 - Earth leakage circuit breaker
overvoltage category
III
standards
IEC 61009-1
IEC 61009-2-1
EN 61009-1
EN 61009-2-1
Etim 7
EC000905 - Earth leakage circuit breaker
Width in number of modular spacings
4
Maximum surge current
0.25 kA
Earthing switch type
Undelayed
Leakage current type
AC
Weee b2c / b2b
Business To Consumer
Rohs information
9AKK106713A5597