Additional Information
Connecting capacity
Busbar 16 / 16 mm²
Conductor 2.5 ... 50 mm²
Flexible 4 ... 35 mm²
Rigid 2.5 ... 50 mm²
Stranded 2.5 ... 50 mm²
curve
C
Data sheet, technical information
9AKK107680A3031
Eclass
V11.0 : 27141901
Package level 1 depth / length
58 mm
Product net depth / length
69
mm
Rohs status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Resistance to vibrations acc
5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
Weee category
5. Small Equipment (No External Dimension More Than 50 cm)
Main
Terminal type
Screw Terminals
Number of protected poles
3
degree of protection
IP20
Enclosure with Cover IP40
Complementary
Accessories available
Yes
Actuator marking
I / O
Actuator type
Toggle
Ambient air temperature
Operation -25 ... +55 °C
Storage -40 ... +70 °C
Cn8
8536 20 90
Declaration of conformity - ce
2CDK400601D2703
Package level 1 gross weight
16 kg
Product net weight
0.42
kg
[in] rated current
80 A
Actuator material
Insulation Group II, Black, Sealable
Package level 1 height
80 mm
Product net width
52.5
mm
[ics] rated service breaking capacity
(400 V AC) 6 kA
Country of origin
Germany (DE)
Environmental conditions
28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
Package level 1 units
carton 1 piece
Package level 1 width
92 mm
tightening torque
3 N·m
Package level 2 depth / length
395 mm
Package level 2 ean
4016779919142
Contact position indication
ON / OFF
Package level 2 gross weight
13.36 kg
Package level 2 height
210 mm
Idea granular category code (igcc)
4897 >> Miniature circuit breakers
Operational voltage
Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
Package level 2 units
crate 36 piece
Instructions and manuals
2CDS207104P0002
mechanical endurance
20000 cycle
Package level 2 width
275 mm
Minimum order quantity
1 piece
Input voltage type
AC
Power supply connection
Arbitrary
Object classification code
F
Rated conditional short-circuit current (inc)
(230 V) 10 kA
(400 V) 20 kA
Package level 1 ean
4016779917704
Housing material
Insulation Group I, RAL 7035
Pollution degree
3
Product net height
88
mm
Rated short-circuit capacity
(AC) 6 kA
(DC) 6 kA
(230 V AC) 6 kA
(400 V AC) 6 kA
mounting position
any
Rated frequency (f)
50 / 60 Hz
Rated impulse withstand voltage (uimp)
4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Mounting on din rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Rated insulation voltage (ui)
acc. to IEC/EN 60664-1 440 V
Power loss
39.2 W
at Rated Operating Conditions per Pole 9.8 W
Rated operational voltage
acc. to IEC 60898-1 400 V AC
acc. to IEC 60947-2 400 V AC
Reach declaration
9AKK107492A1906
Poles description
3
Recommended screw driver
Pozidriv 2
Resistance to shock acc
25g / 2 shocks / 13 ms
Rated ultimate short-circuit breaking capacity (icu)
(230 V AC) 10 kA
(400 V AC) 6 kA
Environment
Built-in depth (t2)
69 mm
Customs tariff number
85362090
Electrical endurance
10000 AC cycle
Energy limiting class
3
Eplan catalog tree
Electrical engineering / Protection devices / General
Certification agency
EN
IEC
Eplan graphical macro
9AKK106713A8196
Eplan macro
9AKK106713A8194
ETIM - 8
EC000042 - Miniature circuit breaker (MCB)
overvoltage category
III
standards
IEC/EN 60898-1
IEC/EN 60947-2
Etim 7
EC000042 - Miniature circuit breaker (MCB)
Width in number of modular spacings
3
Eplan function definition
Circuit breaker / Triple circuit breaker / Triple circuit breaker 1_2_3_4_5_6
Reference ambient air temperature
30 °C
Weee b2c / b2b
Business To Business
E-number (finland)
3210635
Rohs information
2CDK400601D2703
Screw terminal type
Failsafe Bi-directional Cylinder-lift Terminal
Unspsc
39121603
Installation size
acc. to DIN 43880 1
dielectric test voltage
50/60 Hz, 1 min: 2 kV