Main
Accessory category
Interlocking accessory
Device short name
ACP + BA
Complementary
product compatibility
Compact NS630b...1600
Compact NSX100...250
Compact NSX400...630
[ie] rated operational current
AC-12: 4 A AC 440 V
AC-12: 5 A AC 380/415 V
AC-12: 8 A AC 110 V
AC-12: 8 A AC 220/240 V
AC-12: 8 A AC 24 V
AC-12: 8 A AC 48 V
AC-13: 6 A AC 110 V
AC-13: 6 A AC 220/240 V
AC-13: 7 A AC 24 V
AC-13: 7 A AC 48 V
AC-14: 4 A AC 110 V
AC-14: 4 A AC 220/240 V
AC-14: 5 A AC 24 V
AC-14: 5 A AC 48 V
AC-15: 3 A AC 220/240 V
AC-15: 4 A AC 110 V
AC-15: 5 A AC 24 V
AC-15: 5 A AC 48 V
DC-12: 0.4 A DC 250 V
DC-12: 0.6 A DC 110 V
DC-12: 2 A DC 48 V
DC-12: 8 A DC 24 V
DC-13: 2 A 24 V
Interlocked device
NSX400...630
MasterPact NW
NSX100...250
MasterPact NT
Compact NS630b...1600
Compact NS100...630
range compatibility
ComPact (ComPact NS) circuit breaker
ComPact (ComPact NSX) circuit breaker
Masterpact (MasterPact NT) circuit breaker
Masterpact (MasterPact NW) circuit breaker
[ith] conventional thermal current
8 A
Complementary function
Additional contact: transfer to replacement source only if contact is closed
Voluntary transfer to replacement source (e.g. energy management commands)
Product or component type
Interface and control unit
[us] rated supply voltage
220...240 V AC at 50/60 Hz
Output type
Contacts customer: indication of operation in automatic or stop mode
Selection modes
Circuit breaker on N
Circuit breaker on R
Ik degree of protection
Front: IK07 conforming to EN 50102
input type
Contacts customer voluntary order to transfer to source R
Local signalling
Off
On
Fault trip
Test function
By opening the P25M circuit breaker supplying the controller
Operating mode
Automatic operation
Forced operation on replacement source
Forced operation on normal source
Stop (both normal and replacement source off)
Environment
ip degree of protection
IP20 connectors: conforming to EN 60529
IP40 front: conforming to EN 60529
IP30 side: conforming to EN 60529
Range of product
MasterPact NT
NSX100...250
Compact NS100...630
MasterPact NW
Compact NS630b...1600
NSX400...630
standards
IEC 947-5-1