Complementary
[ie] rated operational current
AC-12: 4 A AC 440 V
AC-12: 5 A AC 380/415 V
DC-13: 2 A 24 V
Interlocked device
MasterPact NW
Compact NS100...630
Compact NS630b...1600
MasterPact NT
[ith] conventional thermal current
8 A
Complementary function
Selection of type of normal source (single-phase or three-phase)
Setting of maximum startup time for the replacement source
Voluntary transfer to replacement source (e.g. energy management commands)
Forced normal source if replacement source not operational during peak-tariff
Additional contact: transfer to replacement source only if contact is closed
Product or component type
Control unit
[us] rated supply voltage
220...240 V AC at 50/60 Hz
Genset exerciser
Startup control
Adjustable delayed shutdown
Output type
Contacts customer: indication of operation in automatic or stop mode
Selection modes
Circuit breaker on R
Circuit breaker on N
Ik degree of protection
Front: IK07 conforming to EN 50102
input type
Contacts customer voluntary order to transfer to source R
Local signalling
Fault trip
On
Off
Test function
By pressing the test button on the front of the controller
Operating mode
Forced operation on replacement source
Stop (both normal and replacement source off)
Automatic operation
Forced operation on normal source
Environment
ip degree of protection
IP20 connectors: conforming to EN 60529
IP40 front: conforming to EN 60529
IP30 side: conforming to EN 60529
standards
IEC 947-5-1