Additional Information
csa
CSA-C22.2 No. 107.1-01
shipbuilding approval
DNV GL (EMC B), ABS, LR, RINA, NK, BV
output
2.2 kV (Test Level 3 - asymmetrical)
Main
catalog page
Page 280 (C-4-2019)
foot latch material
POM (Polyoxymethylene)
mtbf (iec 61709, sn 29500)
> 1061000 h (40 °C)
Number of phases
1.00
product family
STEP POWER
gtin
4046356163224
Mounting type
DIN rail mounting
Product type
Power supply
item number
2868651
packing unit
1 pc
degree of protection
IP20
product key
CMPS13
weight per piece (excluding packing)
270 g
weight per piece (including packing)
331.6 g
Complementary
ac frequency range
45 Hz ... 65 Hz
assembly instructions
alignable: 0 mm horizontally, 30 mm vertically
conductor cross section awg max.
12
connection in parallel
yes, for redundancy and increased capacity
depth device depth (din rail mounting)
55 mm (Device depth (DIN rail mounting))
note on status display
UOUT > 21.5 V: LED lights up
status display
"DC OK" LED green
conductor cross section awg min.
24
connection in series
yes
connection method
Screw connection
frequency range
2 GHz ... 3 GHz
frequency range dc
0 Hz
insulation voltage output / pe
500 V DC (routine test)
conductor cross section flexible max.
2.5 mm²
Country of origin
VN
derating
55 °C ... 70 °C (2.5%/K)
horizontal pitch
4 Div.
input fuse
3.15 A (slow-blow, internal)
installation distance right/left
0 mm / 0 mm
operating voltage display
Green LED
protective circuit
Transient surge protection; Varistor
types of signaling
LED
with protective coating
No
conductor cross section flexible min.
0.2 mm²
Handle front plate colour
90 mm
input voltage range ac
85 V AC ... 264 V AC
installation distance top/bottom
30 mm / 30 mm
conductor cross section, rigid max.
2.5 mm²
feedback voltage resistance
≤ 35 V DC
input voltage range dc
95 V DC ... 250 V DC
inrush current
< 15 A (typical)
maximum no-load power dissipation
< 0.7 W
conductor cross section, rigid min.
0.2 mm²
Efficiency
> 86 % (for 230 V AC and nominal values)
typical response time
< 0.5 s
inrush current integral (i2t)
< 0.6 A2s
nominal input voltage range
100 V AC ... 240 V AC
nominal output voltage
24 V DC ±1 %
nominal power consumption
124.3 VA
output characteristic
U/I
output current imax
4.4 A
output power
60 W
tightening torque max
0.6 Nm
width (w)
72 mm
power factor (cos phi)
0.56
screw thread
M3
tightening torque, min
0.5 Nm
voltage type of supply voltage
AC/DC
peak switching voltages nominal load
< 40 mVPP (20 MHz)
recommended breaker for input protection
6 A ... 16 A (Characteristics B, C, D, K)
stripping length
6.5 mm
protection against overvoltage at the output (ovp)
≤ 35 V DC
Minimum order quantity
1 pc
power loss nominal load max.
9.9 W
residual ripple
< 80 mVPP (20 MHz)
rise time
< 0.5 s (UOUT (10 % ... 90 %))
setting range of the output voltage (uset)
22.5 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Housing material
Polycarbonate
mounting position
horizontal DIN rail NS 35, EN 60715
Environment
Ambient air temp for storage/transportation
-40 °C ... 85 °C
china rohs
Environmentally Friendly Use Period = 25;
comments
Criterion A
Customs tariff number
85044083
degree of pollution
2
eclass-11.0
27040701
protection class
II (in closed control cabinet)
Specifications - Environmental Product Compliance:
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”
standards/regulations
EN 61000-6-3
ambient air temperature for operation
-25 °C ... 70 °C (> 55° C derating : 2.5%/K)
contact discharge
6 kV (Test Level 3)
eclass-12.0
27040701
electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
ETIM - 8
EC002540
overvoltage category
III
rail applications
EN 50121-4
reach svhc
Lead 7439-92-1
standard - electrical safety
IEC 62368-1 (SELV)
climatic class
3K3 (in acc. with EN 60721)
discharge in air
8 kV (Test Level 3)
eclass-13.0
27040701
noise immunity
EN 61000-6-2:2005
standard - safe isolation
DIN VDE 0100-410
max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
emitted radio interference in acc. with en 55011
EN 55011 (EN 55022) class B used in industry and residential area / EMC 1
standard - safety of transformers
EN 61558-2-16
unspsc 21.0
39121000
input
4 kV (Test Level 4 - asymmetrical)
shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
standard – electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
low voltage directive
Conformance with Low Voltage Directive 2014/35/EC
standard – limitation of mains harmonic currents
EN 61000-3-2
standard – protection against shock currents, basic requirements for protective separation in electrical equipment
EN 50178
radio interference voltage in acc. with en 55011
EN 55011 (EN 55022) class B used in industry and residential area / EMC 1
standard – safety extra-low voltage
IEC 62368-1 (SELV) und EN 60204-1 (PELV)
test field strength
10 V/m