Additional Information
ul, usa / canada
Class I, Div. 2, Groups A, B, C, D T4A
Main
arrester can be tested with checkmaster from software version:
From SW rev. 1.10
catalog page
Page 173 (C-4-2019)
number of positions
5
flammability rating according to ul 94
V-0
product family
PLUGTRAB PT
gtin
4017918480646
Mounting type
on base element
Product type
Surge protection for information technology
item number
2838775
packing unit
10 pc
degree of protection
IP20
product key
CL3121
wire pairs per module
2
weight per piece (excluding packing)
25.6 g
weight per piece (including packing)
26.593 g
Complementary
capacity (core-core)
typ. 30 pF
complete module depth
65.5 mm
open side panel
No
[in] rated current
450 mA (45 °C)
complete module height
90 mm
connection method
Screw connection (in connection with the base element)
cut-off frequency fg (3 db), sym. in 100 ω system
typ. 60 MHz
nominal voltage un
12 V DC
complete module width
17.7 mm
conductor cross section, flexible [awg]
0.2 mm² ... 2.5 mm²
Country of origin
DE
direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
horizontal pitch
1 Div.
conductor cross section, rigid [awg]
0.2 mm² ... 4 mm²
Handle front plate colour
45 mm
input attenuation ae, sym.
typ. 0.3 dB (≤ 5 MHz / 100 Ω)
tightening torque
0.8 Nm
conductor cross section awg
24 ... 12
max. discharge current imax (8/20) µs maximum (line-earth)
20 kA (in total)
max. discharge current imax (8/20) µs maximum (line-line)
10 kA
max. required back-up fuse
500 mA (T)
nominal discharge current in (8/20) µs (line-line)
10 kA
nominal discharge surge current in (8/20) µs (core-earth)
20 kA (in total)
nominal pulse current ian (10/1000) µs (line-line)
67 A
width (w)
17.7 mm
operating effective current ic at uc
≤ 5 µA
screw thread
M3
Colour
jet black RAL 9005
output voltage limitation at 1 kv/µs (line-line) spike
≤ 55 V
output voltage limitation at 1 kv/µs (line-line) static
≤ 25 V
Minimum order quantity
1 pc
pulse discharge current iimp (10/350) µs
2.5 kA
residual voltage at in (conductor-conductor)
≤ 25 V
residual voltage at in (conductor-ground)
≤ 40 V (with PT 2X2-BE)
depth
52 mm
residual voltage at in (line-signalground)
≤ 25 V (with PT 2X2-BE)
Network type
Male
residual voltage with ian (10/1000) µs (line-line)
≤ 25 V
residual voltage with ian (10/1000) µs (line-signalground)
≤ 25 V
Housing material
PA 6.6
Pollution degree
2
resistance per path
2.2 Ω ±10 %
response time ta
≤ 500 ns
surge protection fault message
none
total discharge current itotal (8/20) µs
20 kA
Environment
altitude
≤ 4000 m (amsl (above mean sea level))
Ambient air temp for storage/transportation
-40 °C ... 85 °C
china rohs
Environmentally Friendly Use Period = 50 years
Customs tariff number
85363010
eclass-11.0
27130807
Specifications - Environmental Product Compliance:
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”
standards/specifications
IEC 61643-21
ambient air temperature for operation
-40 °C ... 85 °C
ETIM - 8
EC000943
overvoltage category
III
reach svhc
Lead 7439-92-1
unspsc 21.0