Additional Information
cccex note
Use in potentially explosive areas is not permitted in China.
certificate
PTB 06 ATEX 2042 U
emc note
EMC: class A product, see manufacturer's declaration in the download area
emc
B
enclosure
Required protection according to the Rules shall be provided upon installation on board
humidity
A
identification
DNV GL
temperature
B
vibration
A
Main
no. of channels
2
gtin
4017918974176
Mounting type
DIN rail mounting
Product type
Media converter
item number
2708614
packing unit
1 pc
degree of protection
IP20
product key
DNC211
weight per piece (excluding packing)
256.9 g
weight per piece (including packing)
270.6 g
transmission medium
Copper
Complementary
bit distortion, input
± 35 % (permitted)
electrical isolation
VCC // RS-485
maximum power dissipation for nominal condition
2.88 W
bit distortion, output
< 6.25 %
connection method
D-SUB-9 female connector
limiting continuous current
0.46 A
conductor cross section flexible max.
2.5 mm²
Country of origin
DE
data direction switching
Automatic control
output description
Alarm output
conductor cross section flexible min.
0.2 mm²
file format/coding
UART (11 Bit, NRZ)
Handle front plate colour
99 mm
supply voltage range
18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block)
tightening torque
0.56 Nm ... 0.79 Nm
conductor cross section, rigid max.
2.5 mm²
max. awg conductor cross section, flexible
14
test voltage data interface/power supply
1.5 kVrms (50 Hz, 1 min.)
conductor cross section, rigid min.
0.2 mm²
maximum receiver sensitivity
-3 dBm (200/230 µm)
nominal supply voltage
24 V DC (in acc. with UL)
output name
Relay output
min. awg conductor cross section, flexible
24
minimum receiver sensitivity
-30 dBm (50/125 µm)
note
Tested by independent PNO test laboratory (PN059-485-01)
output nominal voltage
5 V ±0.25 (50 mA)
Material
PA 6.6-FR
serial transmission speed
≤ 12 Mbps
width (w)
35 mm
number of outputs
1
signal
PROFIBUS
single-wire/terminal point, rigid awg max.
14
stripping length
7 mm
single-wire/terminal point, rigid awg min.
24
Minimum order quantity
1 pc
transmission length
≤ 1200 m (depending on the data rate, with shielded, twisted pair data cable)
depth
105 mm
Wavelength
850 nm
Typical current consumption
120 mA (24 V DC)
Environment
Ambient air temp for storage/transportation
-40 °C ... 85 °C
china rohs
Environmentally Friendly Use Period = 50 years
Customs tariff number
85176200
eclass-11.0
19170411
Specifications - Environmental Product Compliance:
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”
ambient air temperature for operation
-20 °C ... 60 °C
eclass-12.0
19170411
ETIM - 8
EC001467
reach svhc
Lead 7439-92-1
eclass-13.0
19170411
unspsc 21.0
43201500
permissible humidity (operation)
30 % ... 95 % (non-condensing)