Complementary
Ambient air temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Declaration of conformity - ce
2CMT2019-005796
Package level 1 gross weight
34 kg
Product net weight
32
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC000066 - Magnet contactor, AC-switching
Etim 5
EC000066 - Magnet contactor, AC-switching
Package level 1 height
500 mm
Product net width
438
mm
[ics] rated service breaking capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 10000 A
Cb certificate
SEMKO_SE-74013
Package level 1 units
box 1 piece
Package level 1 width
555 mm
Connecting capacity main circuit
Bar 100 mm²
dimension
53540930-7
Cqc certificate
CQC2003010304101933
CQC2015010304752548
Environmental information
1SFC101014D0201
1SAC200046H0008
Horsepower rating ul/csa
(220 ... 240 V AC) Three Phase 400 hp
(440 ... 480 V AC) Three Phase 800 hp
(550 ... 600 V AC) Three Phase 1000 hp
Idea granular category code (igcc)
4758 >> Iec Contactors
Package level 2 units
1 piece
Dnv gl certificate
TAE00001W1
Instructions and manuals
1SFC101002M5501
Number of auxiliary contacts no
2
Maximum operating altitude permissible
Without Derating 3000 m
Maximum operating voltage ul/csa
Main Circuit 1000 V
Lovag certificate
SE-202726
Gl certificate
GL_20263-04HH
Minimum order quantity
1 piece
Maximum mechanical switching frequency
300 cycles per hour
mechanical durability
0.5 million
Number of main contacts no
3
Object classification code
Q
Package level 1 ean
7320500250150
Product net height
392
mm
Rated control circuit voltage (uc)
50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Rated short-time withstand current low voltage (icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 8000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 4500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 10000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 6000 A
Rated frequency (f)
Main Circuit 50 / 60 Hz
Prs certificate
TE_2092_880423_16
Rated impulse withstand voltage (uimp)
Main Circuit 8 kV
Rated insulation voltage (ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 1000 V
Rated operational current ac-1 (ie)
(1000 V) 40 °C 1350 A
(1000 V) 55 °C 1150 A
(1000 V) 70 °C 1000 A
(690 V) 40 °C 1350 A
(690 V) 55 °C 1150 A
(690 V) 70 °C 1000 A
Rated operational current ac-3 (ie)
(415 V) 55 °C 860 A
(440 V) 55 °C 860 A
(500 V) 55 °C 800 A
(690 V) 55 °C 800 A
(1000 V) 55 °C 375 A
(380 / 400 V) 55 °C 860 A
(220 / 230 / 240 V) 55 °C 860
Operate time
Between Coil De-energization and NC Contact Closing 35 ... 55 ms
Between Coil De-energization and NO Contact Opening 35 ... 55 ms
Between Coil Energization and NC Contact Opening 50 ... 80 ms
Between Coil Energization and NO Contact Closing 50 ... 80 ms
Rated making capacity ac-3
10 x Ie AC-3
Rated operational power ac-3 (pe)
(415 V) 500 kW
(440 V) 560 kW
(500 V) 560 kW
(690 V) 800 kW
(1000 V) 560 kW
(380 / 400 V) 475 kW
(220 / 230 / 240 V) 257 kW
Rated operational current dc-1 (ie)
(220 V) 3 Poles in Series, 40 °C 1350 A
(600 V) 3 Poles in Series, 40 °C 1350 A
(850 V) 3 Poles in Series, 40 °C 1350 A
Rated operational voltage
Main Circuit 1000 V
Reach declaration
2CMT2021-006202
Rated operational current dc-3 (ie)
(220 V) 3 Poles in Series, 40 °C 1350 A
(600 V) 3 Poles in Series, 40 °C 1350 A
(850 V) 3 Poles in Series, 40 °C 1350 A
Rated operational current dc-5 (ie)
(220 V) 3 Poles in Series, 40 °C 1350 A
(600 V) 3 Poles in Series, 40 °C 1350 A
(850 V) 3 Poles in Series, 40 °C 1350 A
Ul certificate
UL_20130904-E73397
Ul listing card
UL_E73397
Environment
Ccs certificate
GB14T00030
Coil consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 48 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 48 V·A
Holding at Max. Rated Control Circuit Voltage DC 20.5 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 2450 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 2450 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 2290 V·A
Coil operating limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit
Flexible with Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 1x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 1 x 1 .... 4 mm²
Conventional free-air thermal current (ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1350 A
Customs tariff number
85364900
EAC certificate
9AKK107046A8618
Rina certificate
ELE060313XG_002
Declaration of conformity - ccc
2020980304001303
2020980304001043
ETIM - 8
EC000066 - Power contactor, AC switching
Etim 6
EC000066 - Power contactor, AC switching
Rmrs certificate
9AKK107045A6978
Declaration of conformity - ukca
2CMT2020-006118
Etim 7
EC000066 - Power contactor, AC switching
General use rating ul/csa
(1000 V AC) 1350 A
(600 V AC) 1350 A
Lr certificate
16-20064
E-number (finland)
3707162
Number of auxiliary contacts nc
2
Rohs information
2CMT2021-006277
Maximum electrical switching frequency
(AC-1) 60 cycles per hour
(AC-2 / AC-4) 60 cycles per hour
(AC-3) 60 cycles per hour
Unspsc
39121529