Additional Information
Bv certificate
BV_36353_A0BV
Data sheet, technical information
1SBC100192C0206
Eclass
V11.0 : 27371003
Package level 1 depth / length
262 mm
Product net depth / length
180
mm
Rohs status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Main
Terminal type
Main Circuit: Bars
degree of protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Complementary
Ambient air temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Declaration of conformity - ce
2CMT2015-005439
Package level 1 gross weight
6.4 kg
Product net weight
5.7
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC000066 - Magnet contactor, AC-switching
Etim 5
EC000066 - Magnet contactor, AC-switching
Package level 1 height
212 mm
Product net width
184
mm
[ics] rated service breaking capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 5000 A
Cb certificate
SE-89316
Package level 1 units
box 1 piece
Package level 1 width
212 mm
Connecting capacity main circuit
Flexible 1 x 16 ... 240 mm²
Rigid Al-Cable 1 x 185 ... 240 mm²
Rigid Cu-Cable 2 x 70 ... 185 mm²
dimension
1SFB535001G1123
Cqc certificate
CQC2014010304676670
Idea granular category code (igcc)
4758 >> Iec Contactors
Dnv gl certificate
DNV_E-14043
Instructions and manuals
1SFC101066M0201
Number of auxiliary contacts no
2
Maximum operating altitude permissible
Without Derating 3000 m
Maximum operating voltage ul/csa
Main Circuit 1000 V
Minimum order quantity
1 piece
Maximum mechanical switching frequency
300 cycles per hour
mechanical durability
5 million
Number of main contacts no
4
Object classification code
Q
Package level 1 ean
7320500504345
Product net height
225
mm
Rated control circuit voltage (uc)
50 Hz 24 ... 60 V
60 Hz 24 ... 60 V
DC Operation 20 ... 60 V
Rated short-time withstand current low voltage (icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2960 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 1208 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3700 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1709 A
Rated frequency (f)
Main Circuit 60 Hz
Prs certificate
TE_2092_880423_16
Rated impulse withstand voltage (uimp)
Main Circuit 8 kV
Rated insulation voltage (ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie)
(1000 V) 40 °C 400 A
(1000 V) 60 °C 350 A
(1000 V) 70 °C 290 A
(690 V) 40 °C 525 A
(690 V) 60 °C 425 A
(690 V) 70 °C 350 A
Rated operational current ac-3 (ie)
(415 V) 55 °C 370 A
(440 V) 55 °C 370 A
(380 / 400 V) 55 °C 370 A
(220 / 230 / 240 V) 55 °C 370
Operate time
Between Coil De-energization and NO Contact Opening 45 ... 80 ms
Between Coil Energization and NO Contact Closing 30 ... 60 ms
Rated making capacity ac-3
10 x Ie AC-3
Rated operational power ac-3 (pe)
(415 V) 200 kW
(440 V) 200 kW
(380 / 400 V) 200 kW
(220 / 230 / 240 V) 110 kW
Rated operational voltage
Main Circuit 1000 V
Reach declaration
2CMT2021-006202
Ul certificate
20140910-E73397
Environment
Coil consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 8.5 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 8.5 V·A
Holding at Max. Rated Control Circuit Voltage DC 3 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 475 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 475 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 400 W
Coil operating limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 1 x 1 .... 4 mm²
Conventional free-air thermal current (ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 525 A
Customs tariff number
85364900
EAC certificate
9AKK107046A8618
Rina certificate
ELE060313XG_002
Declaration of conformity - ccc
2020980304001305
ETIM - 8
EC000066 - Power contactor, AC switching
Etim 6
EC000066 - Power contactor, AC switching
Rmrs certificate
9AKK107045A6978
Short-circuit protective devices
gG Type Fuses 630 A
Declaration of conformity - ukca
2CMT2020-006118
Etim 7
EC000066 - Power contactor, AC switching
General use rating ul/csa
(600 V AC) 420 A
Lr certificate
LR_14_70011(E1)
E-number (finland)
3707245
Number of auxiliary contacts nc
2
Rohs information
2CMT2021-006277
Maximum electrical switching frequency
(AC-1) 300 cycles per hour
Unspsc
39121529
Rated breaking capacity ac-3
8 x Ie AC-3