Complementary
Ambient air temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Declaration of conformity - ce
2CMT2015-005439
Package level 1 gross weight
4.6 kg
Product net weight
3.9
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC000066 - Magnet contactor, AC-switching
Etim 5
EC000066 - Magnet contactor, AC-switching
Package level 1 height
289 mm
Product net width
140
mm
[ics] rated service breaking capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3800 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3300 A
Cb certificate
SE-89316
Package level 1 units
box 1 piece
Package level 1 width
263 mm
Connecting capacity main circuit
Flexible 1 x 16 ... 240 mm²
Rigid Al-Cable 1 x 185 ... 240 mm²
Rigid Cu-Cable 1 x 6 ... 300 mm²
dimension
1SFB535001G1060
Cqc certificate
CQC2014010304676670
CQC2014010304673866
Continuous current rating nema
270 A
Environmental information
2CMT004732
1SAC200043H0005
Horsepower rating ul/csa
(200 V AC) Three Phase 75 hp
(208 V AC) Three Phase 75 hp
(220 ... 240 V AC) Three Phase 100 hp
(440 ... 480 V AC) Three Phase 200 hp
(550 ... 600 V AC) Three Phase 250 hp
Idea granular category code (igcc)
4758 >> Iec Contactors
Dnv gl certificate
DNV_E-14043
Instructions and manuals
1SFC100008M0201
Number of auxiliary contacts no
2
Horsepower rating nema
(200 V AC) Three Phase 75 Hp
(230 V AC) Three Phase 100 Hp
(460 V AC) Three Phase 200 Hp
(575 V AC) Three Phase 200 Hp
Maximum operating altitude permissible
Without Derating 3000 m
Maximum operating voltage ul/csa
Main Circuit 1000 V
Gl certificate
GL_95073-14HH
Minimum order quantity
1 piece
Maximum mechanical switching frequency
300 cycles per hour
mechanical durability
5 million
Number of main contacts no
3
Object classification code
Q
Package level 1 ean
7320500481127
Nema size
5
Product net height
225
mm
Rated control circuit voltage (uc)
50 Hz 48 ... 130 V
60 Hz 48 ... 130 V
DC Operation 48 ... 130 V
Rated short-time withstand current low voltage (icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2120 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 400 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 865 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2650 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1224 A
Rated frequency (f)
Main Circuit 50 / 60 Hz
Prs certificate
TE_2092_880423_16
Rated impulse withstand voltage (uimp)
Main Circuit 8 kV
Rated insulation voltage (ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie)
(1000 V) 40 °C 350 A
(1000 V) 55 °C 300 A
(1000 V) 60 °C 300 A
(1000 V) 70 °C 240 A
(690 V) 40 °C 400 A
(690 V) 55 °C 350 A
(690 V) 70 °C 290 A
Rated operational current ac-3 (ie)
(415 V) 55 °C 265 A
(440 V) 55 °C 265 A
(500 V) 55 °C 250 A
(690 V) 55 °C 250 A
(1000 V) 55 °C 113 A
(380 / 400 V) 55 °C 265 A
(220 / 230 / 240 V) 55 °C 265
Operate time
Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Rated making capacity ac-3
10 x Ie AC-3
Rated operational power ac-3 (pe)
(415 V) 132 kW
(440 V) 160 kW
(500 V) 160 kW
(690 V) 200 kW
(1000 V) 160 kW
(380 / 400 V) 132 kW
(220 / 230 / 240 V) 75 kW
Rated operational current dc-1 (ie)
(110 V) 2 Poles in Series, 40 °C 350 A
(220 V) 3 Poles in Series, 40 °C 350 A
Rated operational voltage
Main Circuit 1000 V
Reach declaration
2CMT2021-006202
Rated operational current dc-3 (ie)
(110 V) 2 Poles in Series, 40 °C 350 A
(220 V) 3 Poles in Series, 40 °C 350 A
Rated operational current dc-5 (ie)
(110 V) 2 Poles in Series, 40 °C 350 A
(220 V) 3 Poles in Series, 40 °C 350 A
Ul certificate
20121217-E36588
Ul listing card
UL_E36588
Environment
Ccs certificate
GB14T00030
Coil consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 17 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 17 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 150 W
Coil operating limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²
Conventional free-air thermal current (ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 400 A
Customs tariff number
85364900
EAC certificate
9AKK107046A8618
Rina certificate
ELE060313XG_002
Declaration of conformity - ccc
2020980304001305
2020980304001068
ETIM - 8
EC000066 - Power contactor, AC switching
Etim 6
EC000066 - Power contactor, AC switching
Rmrs certificate
9AKK107045A6978
Short-circuit protective devices
gG Type Fuses 500 A
Declaration of conformity - ukca
2CMT2020-006118
Etim 7
EC000066 - Power contactor, AC switching
General use rating ul/csa
(600 V AC) 350 A
Dnv certificate
DNV_E-14043
Lr certificate
LR_14_70011(E1)
E-number (finland)
3706472
Number of auxiliary contacts nc
2
Rohs information
2CMT2021-006277
Maximum electrical switching frequency
(AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Unspsc
39121529
Rated breaking capacity ac-3
8 x Ie AC-3