Additional Information
Bv certificate
BV_36353_A0BV
Data sheet, technical information
1SBC100192C0206
E-number (sweden)
3210337
Eclass
V11.0 : 27371003
Package level 1 depth / length
238 mm
Product net depth / length
152.5
mm
Rohs status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Main
Terminal type
Main Circuit: Bars
degree of protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Complementary
Ambient air temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Declaration of conformity - ce
2CMT2015-005440
Package level 1 gross weight
3.9 kg
Product net weight
3.3
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC000066 - Magnet contactor, AC-switching
Etim 5
EC000066 - Magnet contactor, AC-switching
Package level 1 height
180 mm
Product net width
140
mm
[ics] rated service breaking capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 A
Cb certificate
SE-82315
Package level 1 units
box 1 piece
Package level 1 width
166 mm
Connecting capacity main circuit
Flexible 1 x 6 ... 120 mm²
Rigid Al-Cable 1 x 95 ... 185 mm²
Rigid Cu-Cable 1 x 6 ... 150 mm²
dimension
1SFB535001G1122
Cqc certificate
CQC2014010304676685
End of life instructions
1SFC100112M0001
Idea granular category code (igcc)
4758 >> Iec Contactors
Dnv gl certificate
DNV_E-14043
Number of auxiliary contacts no
1
Maximum operating altitude permissible
Without Derating 3000 m
Maximum operating voltage ul/csa
Main Circuit 1000 V
Minimum order quantity
1 piece
Maximum mechanical switching frequency
300 cycles per hour
mechanical durability
5 million
Number of main contacts no
4
Object classification code
Q
Package level 1 ean
7320500503690
Product net height
195.6
mm
Rated control circuit voltage (uc)
50 Hz 250 ... 500 V
60 Hz 250 ... 500 V
DC Operation 250 ... 500 V
Rated short-time withstand current low voltage (icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1640 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 670 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2050 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 947 A
Rated frequency (f)
Main Circuit 50 Hz
Prs certificate
TE_2092_880423_16
Rated impulse withstand voltage (uimp)
Main Circuit 8 kV
Rated insulation voltage (ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie)
(1000 V) 40 °C 275 A
(1000 V) 60 °C 250 A
(1000 V) 70 °C 200 A
(690 V) 40 °C 350 A
(690 V) 60 °C 300 A
(690 V) 70 °C 240 A
Rated operational current ac-3 (ie)
(415 V) 55 °C 205 A
(440 V) 55 °C 205 A
(380 / 400 V) 55 °C 205 A
(220 / 230 / 240 V) 55 °C 205
Operate time
Between Coil De-energization and NO Contact Opening 45 ... 80 ms
Between Coil Energization and NO Contact Closing 25 ... 60 ms
Rated making capacity ac-3
10 x Ie AC-3
Rated operational power ac-3 (pe)
(415 V) 110 kW
(440 V) 132 kW
(380 / 400 V) 110 kW
(220 / 230 / 240 V) 55 kW
Rated operational voltage
Main Circuit 1000 V
Reach declaration
2CMT2021-006202
Ul certificate
20140925-E73397
Environment
Coil consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·A
Holding at Max. Rated Control Circuit Voltage DC 3.9 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 260 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 260 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 230 W
Coil operating limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²
Conventional free-air thermal current (ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 350 A
Customs tariff number
85364900
EAC certificate
9AKK107046A8618
Rina certificate
ELE060313XG_002
Declaration of conformity - ccc
2020980304001306
Environmental product declaration - epd
1SFC100095D0201
ETIM - 8
EC000066 - Power contactor, AC switching
Etim 6
EC000066 - Power contactor, AC switching
Rmrs certificate
9AKK107045A6978
Short-circuit protective devices
gG Type Fuses 400 A
Circular design principles recyclability rate
Design for Closing Resource Loops - Standard EN45555 - 79.2 %
Declaration of conformity - ukca
2CMT2020-006118
Etim 7
EC000066 - Power contactor, AC switching
General use rating ul/csa
(600 V AC) 250 A
Lr certificate
LR_14_70011(E1)
E-number (finland)
3707217
Improved resource efficiency for customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line - Achieved
Number of auxiliary contacts nc
1
Rohs information
2CMT2021-006277
Maximum electrical switching frequency
(AC-1) 300 cycles per hour
Unspsc
39121529
E-number (norway)
3210337
Group waste to landfill target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility - Achieved
Rated breaking capacity ac-3
8 x Ie AC-3