Additional Information
Bv certificate
BV_36353_A0BV
Data sheet, technical information
1SBC100192C0206
E-number (sweden)
3210139
Eclass
V11.0 : 27371003
Package level 1 depth / length
258 mm
Product net depth / length
152
mm
Rohs status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Main
Terminal type
Main Circuit: Bars
degree of protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Complementary
Ambient air temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Declaration of conformity - ce
2CMT2015-005439
Package level 1 gross weight
3 kg
Product net weight
2.4
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC000066 - Magnet contactor, AC-switching
Etim 5
EC000066 - Magnet contactor, AC-switching
Package level 1 height
235 mm
Product net width
105
mm
[ics] rated service breaking capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A
Cb certificate
SE-82315
Package level 1 units
box 1 piece
Package level 1 width
160 mm
Connecting capacity main circuit
Flexible 1 x 6 ... 120 mm²
Rigid Cu-Cable 2 x 50 ... 120 mm²
dimension
1SFB535001G1056
Cqc certificate
CQC2014010304676685
CQC2014010304724672
Environmental information
2CMT004732
1SAC200042H0004
End of life instructions
1SFC100112M0001
Horsepower rating ul/csa
(200 V AC) Three Phase 60 hp
(208 V AC) Three Phase 60 hp
(220 ... 240 V AC) Three Phase 75 hp
(440 ... 480 V AC) Three Phase 150 hp
(550 ... 600 V AC) Three Phase 200 hp
Idea granular category code (igcc)
4758 >> Iec Contactors
Dnv gl certificate
DNV_E-14043
Instructions and manuals
1SFC100008M0201
Maximum operating altitude permissible
Without Derating 3000 m
Maximum operating voltage ul/csa
Main Circuit 1000 V
Gl certificate
GL_95072-14HH
Minimum order quantity
1 piece
Maximum mechanical switching frequency
300 cycles per hour
mechanical durability
5 million
Number of main contacts no
3
Object classification code
Q
Package level 1 ean
7320500480533
Product net height
196
mm
Rated control circuit voltage (uc)
50 Hz 250 ... 500 V
60 Hz 250 ... 500 V
DC Operation 250 ... 500 V
Rated short-time withstand current low voltage (icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1640 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 670 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2050 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 947 A
Rated frequency (f)
Main Circuit 50 / 60 Hz
Prs certificate
TE_2092_880423_16
Rated impulse withstand voltage (uimp)
Main Circuit 8 kV
Rated insulation voltage (ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie)
(1000 V) 40 °C 275 A
(1000 V) 55 °C 250 A
(1000 V) 60 °C 250 A
(1000 V) 70 °C 200 A
(690 V) 40 °C 350 A
(690 V) 55 °C 300 A
(690 V) 70 °C 240 A
Rated operational current ac-3 (ie)
(415 V) 55 °C 205 A
(440 V) 55 °C 205 A
(500 V) 55 °C 186 A
(690 V) 55 °C 165 A
(1000 V) 55 °C 100 A
(380 / 400 V) 55 °C 205 A
(220 / 230 / 240 V) 55 °C 205
Operate time
Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Rated making capacity ac-3
10 x Ie AC-3
Rated operational power ac-3 (pe)
(415 V) 110 kW
(440 V) 132 kW
(500 V) 132 kW
(690 V) 160 kW
(1000 V) 132 kW
(380 / 400 V) 110 kW
(220 / 230 / 240 V) 55 kW
Rated operational current dc-1 (ie)
(110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated operational voltage
Main Circuit 1000 V
Reach declaration
2CMT2021-006202
Rated operational current dc-3 (ie)
(110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Rated operational current dc-5 (ie)
(110 V) 2 Poles in Series, 40 °C 275 A
(220 V) 3 Poles in Series, 40 °C 275 A
Ul certificate
20121023-E36588
Ul listing card
UL_E36588
Environment
Ccs certificate
GB14T00030
Coil consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·A
Holding at Max. Rated Control Circuit Voltage DC 3.9 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 260 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 260 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 230 W
Coil operating limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit
Flexible with Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 1 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²
Conventional free-air thermal current (ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 350 A
Customs tariff number
85364900
EAC certificate
9AKK107046A8618
Rina certificate
ELE060313XG_002
Declaration of conformity - ccc
2020980304001306
2020980304001071
Environmental product declaration - epd
1SFC100095D0201
ETIM - 8
EC000066 - Power contactor, AC switching
Etim 6
EC000066 - Power contactor, AC switching
Rmrs certificate
9AKK107045A6978
Short-circuit protective devices
gG Type Fuses 400 A
Circular design principles recyclability rate
Design for Closing Resource Loops - Standard EN45555 - 79.2 %
Declaration of conformity - ukca
2CMT2020-006118
Etim 7
EC000066 - Power contactor, AC switching
General use rating ul/csa
(600 V AC) 300 A
Kc certificate
9AKK107046A9912
Dnv certificate
DNV_E-14043
Lr certificate
LR_14_70011(E1)
E-number (finland)
3706464
Improved resource efficiency for customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line - Achieved
Rohs information
2CMT2021-006277
Maximum electrical switching frequency
(AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Unspsc
39121529
E-number (norway)
3210139
Group waste to landfill target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility - Achieved
Rated breaking capacity ac-3
8 x Ie AC-3