All categories
Compare Cart

1SFL487002R1422 - CONTACTOR AF190-30-22-14 250-500V - ABB

Expected in 2-4 weeks
1SFL487002R1422 - CONTACTOR AF190-30-22-14 250-500V - ABB - CONTACTOR AF190-30-22-14 250-500V - ABB - 0
1SFL487002R1422 - CONTACTOR AF190-30-22-14 250-500V - ABB
358,64 €
358,64 € incl. VAT
Text About:
CONTACTOR AF190-30-22-14 250-500V - ABB
358,64 €
SPECIFICATIONS
Additional Information
Bv certificate BV_36353_A0BV
Data sheet, technical information 1SBC100192C0206
Eclass V11.0 : 27371003
Package level 1 depth / length 258 mm
Product net depth / length 152
mm
Rohs status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Main
Terminal type Main Circuit: Bars
degree of protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Complementary
Ambient air temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Declaration of conformity - ce 2CMT2015-005439
Package level 1 gross weight 3 kg
Product net weight 2.4
kg
Cad dimensional drawing 2CDC001079B0201
Etim 4 EC000066 - Magnet contactor, AC-switching
Etim 5 EC000066 - Magnet contactor, AC-switching
Package level 1 height 235 mm
Product net width 105
mm
[ics] rated service breaking capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A
Cb certificate SE-82315
Package level 1 units box 1 piece
Package level 1 width 160 mm
Connecting capacity main circuit Flexible 2 x 50 ... 95 mm²
Rigid Al-Cable 1 x 95 ... 185 mm²
Rigid Cu-Cable 1 x 6 ... 150 mm²
dimension 1SFB535001G1056
Cqc certificate CQC2014010304676685


CQC2014010304724672
Environmental information 2CMT004732


1SAC200042H0004
End of life instructions 1SFC100112M0001
Horsepower rating ul/csa (200 V AC) Three Phase 50 hp
(208 V AC) Three Phase 50 hp
(220 ... 240 V AC) Three Phase 60 hp
(440 ... 480 V AC) Three Phase 125 hp
(550 ... 600 V AC) Three Phase 150 hp
Idea granular category code (igcc) 4758 >> Iec Contactors
Dnv gl certificate DNV_E-14043
Instructions and manuals 1SFC100008M0201
Number of auxiliary contacts no 2
Maximum operating altitude permissible Without Derating 3000 m
Maximum operating voltage ul/csa Main Circuit 1000 V
Gl certificate GL_95072-14HH
Minimum order quantity 1 piece
Maximum mechanical switching frequency 300 cycles per hour
mechanical durability 5 million
Number of main contacts no 3
Object classification code Q
Package level 1 ean 7320500480496
Product net height 196
mm
Rated control circuit voltage (uc) 50 Hz 250 ... 500 V
60 Hz 250 ... 500 V
DC Operation 250 ... 500 V
Rated short-time withstand current low voltage (icw) at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
Rated frequency (f) Main Circuit 50 / 60 Hz
Prs certificate TE_2092_880423_16
Rated impulse withstand voltage (uimp) Main Circuit 8 kV
Rated breaking capacity ac-3e 8.5 x Ie AC-3e
Rated insulation voltage (ui) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie) (1000 V) 40 °C 250 A
(1000 V) 55 °C 225 A
(1000 V) 60 °C 225 A
(1000 V) 70 °C 185 A
(690 V) 40 °C 275 A
(690 V) 55 °C 250 A
(690 V) 60 °C 250 A
(690 V) 70 °C 200 A
Rated operational current ac-3 (ie) (415 V) 55 °C 190 A
(440 V) 55 °C 190 A
(500 V) 55 °C 156 A
(690 V) 55 °C 135 A
(1000 V) 55 °C 85 A
(380 / 400 V) 55 °C 190 A
(220 / 230 / 240 V) 55 °C 190
Operate time Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Rated making capacity ac-3 10 x Ie AC-3
Rated making capacity ac-3e 12 x Ie AC-3e
Rated operational power ac-3 (pe) (415 V) 90 kW
(440 V) 110 kW
(500 V) 110 kW
(690 V) 132 kW
(1000 V) 110 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW
Rated operational current dc-1 (ie) (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated operational voltage Main Circuit 1000 V
Reach declaration 2CMT2021-006202
Rated operational current dc-3 (ie) (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated operational current ac-3e (ie) (415 V) 60 °C 190 A
(440 V) 60 °C 190 A
(500 V) 60 °C 135 A
(690 V) 60 °C 135 A
(1000 V) 60 °C 85 A
(380 / 400 V) 60 °C 190 A
(220 / 230 / 240 V) 60 °C 190 A
Rated operational current dc-5 (ie) (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated operational power ac-3e (pe) (415 V) 90 kW
(440 V) 110 kW
(500 V) 110 kW
(690 V) 132 kW
(1000 V) 110 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW
Ul certificate 20121023-E36588
Ul listing card UL_E36588
Environment
Ccs certificate GB14T00030
Coil consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·A
Holding at Max. Rated Control Circuit Voltage DC 3.9 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 260 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 260 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 230 W
Coil operating limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 1 x 1 ... 4 mm²
Stranded 1 x 1 .... 4 mm²
Conventional free-air thermal current (ith) acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A
Customs tariff number 85364900
EAC certificate 9AKK107046A8618
Rina certificate ELE060313XG_002
Declaration of conformity - ccc 2020980304001306


2020980304001071
Environmental product declaration - epd 1SFC100095D0201
ETIM - 8 EC000066 - Power contactor, AC switching
Etim 6 EC000066 - Power contactor, AC switching
Rmrs certificate 9AKK107045A6978
Short-circuit protective devices gG Type Fuses 355 A
Circular design principles recyclability rate Design for Closing Resource Loops - Standard EN45555 - 79.2 %
Declaration of conformity - ukca 2CMT2020-006118
Etim 7 EC000066 - Power contactor, AC switching
General use rating ul/csa (600 V AC) 250 A
Kc certificate 9AKK107046A9912
Dnv certificate DNV_E-14043
Lr certificate LR_14_70011(E1)
E-number (finland) 3706398
Improved resource efficiency for customers Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line - Achieved
Number of auxiliary contacts nc 2
Rohs information 2CMT2021-006277
Maximum electrical switching frequency (AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Unspsc 39121529
Group waste to landfill target Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility - Achieved
Rated breaking capacity ac-3 8 x Ie AC-3
Recently viewed
358,64 €
358,64 € incl. VAT
Expected in 2-4 weeks