1SFL487002R1200 - CONTACTOR AF190-30-00-12 48-130V - ABB

Expected in 2-4 weeks
1SFL487002R1200 - CONTACTOR AF190-30-00-12 48-130V - ABB - CONTACTOR AF190-30-00-12 48-130V - ABB - 0
1SFL487002R1200 - CONTACTOR AF190-30-00-12 48-130V - ABB
306,75 € excl. VAT
374,24 € incl. VAT
Text About:
CONTACTOR AF190-30-00-12 48-130V - ABB
374,24 €
SPECIFICATIONS
Additional Information
Bv certificate BV_36353_A0BV
Data sheet, technical information 1SBC100192C0206
E-number (sweden) 3210129
Eclass V11.0 : 27371003
Package level 1 depth / length 258 mm
Product net depth / length 152
mm
Rohs status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Main
Terminal type Main Circuit: Bars
degree of protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Complementary
Ambient air temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Declaration of conformity - ce 2CMT2015-005439
Package level 1 gross weight 3 kg
Product net weight 2.4
kg
Cad dimensional drawing 2CDC001079B0201
Etim 4 EC000066 - Magnet contactor, AC-switching
Etim 5 EC000066 - Magnet contactor, AC-switching
Package level 1 height 235 mm
Product net width 105
mm
[ics] rated service breaking capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A
Cb certificate SE-82315
Package level 1 units box 1 piece
Package level 1 width 160 mm
Connecting capacity main circuit Flexible 1 x 6 ... 120 mm²
Rigid Cu-Cable 2 x 50 ... 120 mm²
dimension 1SFB535001G1056
Cqc certificate CQC2014010304676685


CQC2014010304724672
Environmental information 2CMT004732


1SAC200042H0004
End of life instructions 1SFC100112M0001
Horsepower rating ul/csa (200 V AC) Three Phase 50 hp
(208 V AC) Three Phase 50 hp
(220 ... 240 V AC) Three Phase 60 hp
(440 ... 480 V AC) Three Phase 125 hp
(550 ... 600 V AC) Three Phase 150 hp
Idea granular category code (igcc) 4758 >> Iec Contactors
Dnv gl certificate DNV_E-14043
Instructions and manuals 1SFC100008M0201
Maximum operating altitude permissible Without Derating 3000 m
Maximum operating voltage ul/csa Main Circuit 1000 V
Gl certificate GL_95072-14HH
Minimum order quantity 1 piece
Maximum mechanical switching frequency 300 cycles per hour
mechanical durability 5 million
Number of main contacts no 3
Object classification code Q
Package level 1 ean 7320500480380
Product net height 196
mm
Rated control circuit voltage (uc) 50 Hz 48 ... 130 V
60 Hz 48 ... 130 V
DC Operation 48 ... 130 V
Rated short-time withstand current low voltage (icw) at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
Rated frequency (f) Main Circuit 50 / 60 Hz
Prs certificate TE_2092_880423_16
Rated impulse withstand voltage (uimp) Main Circuit 8 kV
Rated breaking capacity ac-3e 8.5 x Ie AC-3e
Rated insulation voltage (ui) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie) (1000 V) 40 °C 250 A
(1000 V) 55 °C 225 A
(1000 V) 60 °C 225 A
(1000 V) 70 °C 185 A
(690 V) 40 °C 275 A
(690 V) 55 °C 250 A
(690 V) 60 °C 250 A
(690 V) 70 °C 200 A
Rated operational current ac-3 (ie) (415 V) 55 °C 190 A
(440 V) 55 °C 190 A
(500 V) 55 °C 156 A
(690 V) 55 °C 135 A
(1000 V) 55 °C 85 A
(380 / 400 V) 55 °C 190 A
(220 / 230 / 240 V) 55 °C 190
Operate time Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Rated making capacity ac-3 10 x Ie AC-3
Rated making capacity ac-3e 12 x Ie AC-3e
Rated operational power ac-3 (pe) (415 V) 90 kW
(440 V) 110 kW
(500 V) 110 kW
(690 V) 132 kW
(1000 V) 110 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW
Rated operational current dc-1 (ie) (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated operational voltage Main Circuit 1000 V
Reach declaration 2CMT2021-006202
Rated operational current dc-3 (ie) (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated operational current ac-3e (ie) (415 V) 60 °C 190 A
(440 V) 60 °C 190 A
(500 V) 60 °C 135 A
(690 V) 60 °C 135 A
(1000 V) 60 °C 85 A
(380 / 400 V) 60 °C 190 A
(220 / 230 / 240 V) 60 °C 190 A
Rated operational current dc-5 (ie) (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated operational power ac-3e (pe) (415 V) 90 kW
(440 V) 110 kW
(500 V) 110 kW
(690 V) 132 kW
(1000 V) 110 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW
Ul certificate 20121023-E36588
Ul listing card UL_E36588
Environment
Ccs certificate GB14T00030
Coil consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 4 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 4 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 150 W
Coil operating limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 1 x 1 ... 4 mm²
Stranded 1 x 1 .... 4 mm²
Conventional free-air thermal current (ith) acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A
Customs tariff number 85364900
EAC certificate 9AKK107046A8618
Rina certificate ELE060313XG_002
Declaration of conformity - ccc 2020980304001306


2020980304001071
Environmental product declaration - epd 1SFC100095D0201
ETIM - 8 EC000066 - Power contactor, AC switching
Etim 6 EC000066 - Power contactor, AC switching
Rmrs certificate 9AKK107045A6978
Short-circuit protective devices gG Type Fuses 355 A
Circular design principles recyclability rate Design for Closing Resource Loops - Standard EN45555 - 79.2 %
Declaration of conformity - ukca 2CMT2020-006118
Etim 7 EC000066 - Power contactor, AC switching
General use rating ul/csa (600 V AC) 250 A
Kc certificate 9AKK107046A9912
Dnv certificate DNV_E-14043
Lr certificate LR_14_70011(E1)
E-number (finland) 3706390
Improved resource efficiency for customers Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line - Achieved
Rohs information 2CMT2021-006277
Maximum electrical switching frequency (AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Unspsc 39121529
E-number (norway) 3210129
Group waste to landfill target Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility - Achieved
Rated breaking capacity ac-3 8 x Ie AC-3