All categories
Compare Cart

1SFL447001R1211 - CONTACTOR AF140-30-11-12 48-130V - ABB

Expected in 2-4 weeks
1SFL447001R1211 - CONTACTOR AF140-30-11-12 48-130V - ABB - CONTACTOR AF140-30-11-12 48-130V - ABB - 0
1SFL447001R1211 - CONTACTOR AF140-30-11-12 48-130V - ABB
261,47 € excl. VAT
319,00 € incl. VAT
Text About:
CONTACTOR AF140-30-11-12 48-130V - ABB
319,00 €
SPECIFICATIONS
Additional Information
Bv certificate BV_36353_A0BV
Data sheet, technical information 1SBC100192C0206
Eclass V11.0 : 27371003
Package level 1 depth / length 216 mm
Product net depth / length 126
mm
Rohs status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Main
Terminal type Double Clamp
degree of protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Complementary
Ambient air temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Declaration of conformity - ce 2CMT2015-005439
Package level 1 gross weight 1.75 kg
Product net weight 1.55
kg
Cad dimensional drawing 2CDC001079B0201
Etim 4 EC000066 - Magnet contactor, AC-switching
Etim 5 EC000066 - Magnet contactor, AC-switching
Package level 1 height 150 mm
Product net width 90
mm
[ics] rated service breaking capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A
Cb certificate SEMKO_SE-70479M1
Package level 1 units box 1 piece
Package level 1 width 207 mm
Connecting capacity main circuit Flexible 2 x 10 ... 70 mm²
Rigid Cu-Cable 2 x 10 ... 95 mm²
dimension 1SFB535001G1051
Cqc certificate CQC2013010304604055
Continuous current rating nema 135 A
Environmental information 2CMT004732


1SAC200032H0002
End of life instructions 1SFC100112M0001
Horsepower rating ul/csa (200 V AC) Three Phase 40 hp
(208 V AC) Three Phase 40 hp
(220 ... 240 V AC) Three Phase 50 hp
(440 ... 480 V AC) Three Phase 100 hp
(550 ... 600 V AC) Three Phase 125 hp
Idea granular category code (igcc) 4758 >> Iec Contactors
Dnv gl certificate DNV_E-14043
Instructions and manuals 1SFC100003M0201
Number of auxiliary contacts no 1
Horsepower rating nema (200 V AC) Three Phase 40 Hp
(230 V AC) Three Phase 50 Hp
(460 V AC) Three Phase 100 Hp
(575 V AC) Three Phase 100 Hp
Maximum operating altitude permissible Without Derating 3000 m
Maximum operating voltage ul/csa Main Circuit 600 V
Gl certificate DNV_E-14043
Minimum order quantity 1 piece
Maximum mechanical switching frequency 300 cycles per hour
mechanical durability 5 million
Number of main contacts no 3
Object classification code Q
Package level 1 ean 7320500476932
Nema size 4
Product net height 150
mm
Rated control circuit voltage (uc) 50 Hz 48 ... 130 V
60 Hz 48 ... 130 V
DC Operation 48 ... 130 V
Rated short-time withstand current low voltage (icw) at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
Rated frequency (f) Main Circuit 50 / 60 Hz
Prs certificate TE_2092_880423_16
Rated impulse withstand voltage (uimp) Main Circuit 8 kV
Rated breaking capacity ac-3e 8.5 x Ie AC-3e
Rated insulation voltage (ui) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie) (690 V) 40 °C 200 A
(690 V) 70 °C 160 A
Rated operational current ac-3 (ie) (415 V) 55 °C 140 A
(440 V) 55 °C 140 A
(500 V) 55 °C 130 A
(690 V) 55 °C 80 A
(380 / 400 V) 55 °C 140 A
(220 / 230 / 240 V) 55 °C 140
Operate time Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Rated making capacity ac-3 10 x Ie AC-3
Rated making capacity ac-3e 12 x Ie AC-3e
Rated operational power ac-3 (pe) (415 V) 75 kW
(440 V) 90 kW
(500 V) 90 kW
(690 V) 75 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 37 kW
Rated operational current dc-1 (ie) (110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 A
Rated operational voltage Main Circuit 690 V
Reach declaration 2CMT2021-006202
Rated operational current dc-3 (ie) (110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 A
Rated operational current ac-3e (ie) (415 V) 60 °C 140 A
(440 V) 60 °C 140 A
(500 V) 60 °C 130 A
(690 V) 60 °C 80 A
(380 / 400 V) 60 °C 140 A
(220 / 230 / 240 V) 60 °C 140 A
Rated operational current dc-5 (ie) (110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 A
Rated operational power ac-3e (pe) (415 V) 75 kW
(440 V) 90 kW
(500 V) 90 kW
(690 V) 75 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 37 kW
Ul certificate 20120925-E36588
Ul listing card UL_E36588
Environment
Ccs certificate GB14T00030
Coil consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 4 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 4 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 150 W
Coil operating limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 1x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 1 x 1 .... 4 mm²
Conventional free-air thermal current (ith) acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A
Customs tariff number 85364900
EAC certificate 9AKK107046A8618
Rina certificate ELE060313XG_002
Declaration of conformity - ccc 2020980304001304
Environmental product declaration - epd 1SFC100092D0201
ETIM - 8 EC000066 - Power contactor, AC switching
Etim 6 EC000066 - Power contactor, AC switching
Rmrs certificate 9AKK107045A6978
Short-circuit protective devices gG Type Fuses 315 A
Circular design principles recyclability rate Design for Closing Resource Loops - Standard EN45555 - 87.8 %
Declaration of conformity - ukca 2CMT2020-006118
Etim 7 EC000066 - Power contactor, AC switching
General use rating ul/csa (600 V AC) 200 A
Dnv certificate DNV_E-14043
Lr certificate LR_14_70011(E1)
E-number (finland) 3706189
Improved resource efficiency for customers Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line - Achieved
Number of auxiliary contacts nc 1
Rohs information 2CMT2021-006277
Maximum electrical switching frequency (AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Unspsc 39121529
E-number (norway) 4117621
Group waste to landfill target Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility - Achieved
Rated breaking capacity ac-3 8 x Ie AC-3
Recently viewed
261,47 € excl. VAT
319,00 € incl. VAT
Expected in 2-4 weeks