Complementary
Ambient air temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... +70 °C
Declaration of conformity - ce
2CMT2015-005439
Package level 1 gross weight
1.75 kg
Product net weight
1.55
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC000066 - Magnet contactor, AC-switching
Etim 5
EC000066 - Magnet contactor, AC-switching
Package level 1 height
150 mm
Product net width
90
mm
[ics] rated service breaking capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A
Cb certificate
SEMKO_SE-70479M1
Package level 1 units
box 1 piece
Package level 1 width
207 mm
Connecting capacity main circuit
Flexible 2 x 10 ... 70 mm²
Rigid Cu-Cable 2 x 10 ... 95 mm²
dimension
1SFB535001G1051
Cqc certificate
CQC2013010304604055
Continuous current rating nema
135 A
Environmental information
2CMT004732
1SAC200032H0002
End of life instructions
1SFC100112M0001
Horsepower rating ul/csa
(200 V AC) Three Phase 40 hp
(208 V AC) Three Phase 40 hp
(220 ... 240 V AC) Three Phase 50 hp
(440 ... 480 V AC) Three Phase 100 hp
(550 ... 600 V AC) Three Phase 125 hp
Idea granular category code (igcc)
4758 >> Iec Contactors
Dnv gl certificate
DNV_E-14043
Instructions and manuals
1SFC100003M0201
Number of auxiliary contacts no
1
Horsepower rating nema
(200 V AC) Three Phase 40 Hp
(230 V AC) Three Phase 50 Hp
(460 V AC) Three Phase 100 Hp
(575 V AC) Three Phase 100 Hp
Maximum operating altitude permissible
Without Derating 3000 m
Maximum operating voltage ul/csa
Main Circuit 600 V
Gl certificate
DNV_E-14043
Minimum order quantity
1 piece
Maximum mechanical switching frequency
300 cycles per hour
mechanical durability
5 million
Number of main contacts no
3
Object classification code
Q
Package level 1 ean
7320500476932
Nema size
4
Product net height
150
mm
Rated control circuit voltage (uc)
50 Hz 48 ... 130 V
60 Hz 48 ... 130 V
DC Operation 48 ... 130 V
Rated short-time withstand current low voltage (icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
Rated frequency (f)
Main Circuit 50 / 60 Hz
Prs certificate
TE_2092_880423_16
Rated impulse withstand voltage (uimp)
Main Circuit 8 kV
Rated breaking capacity ac-3e
8.5 x Ie AC-3e
Rated insulation voltage (ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated operational current ac-1 (ie)
(690 V) 40 °C 200 A
(690 V) 70 °C 160 A
Rated operational current ac-3 (ie)
(415 V) 55 °C 140 A
(440 V) 55 °C 140 A
(500 V) 55 °C 130 A
(690 V) 55 °C 80 A
(380 / 400 V) 55 °C 140 A
(220 / 230 / 240 V) 55 °C 140
Operate time
Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Rated making capacity ac-3
10 x Ie AC-3
Rated making capacity ac-3e
12 x Ie AC-3e
Rated operational power ac-3 (pe)
(415 V) 75 kW
(440 V) 90 kW
(500 V) 90 kW
(690 V) 75 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 37 kW
Rated operational current dc-1 (ie)
(110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 A
Rated operational voltage
Main Circuit 690 V
Reach declaration
2CMT2021-006202
Rated operational current dc-3 (ie)
(110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 A
Rated operational current ac-3e (ie)
(415 V) 60 °C 140 A
(440 V) 60 °C 140 A
(500 V) 60 °C 130 A
(690 V) 60 °C 80 A
(380 / 400 V) 60 °C 140 A
(220 / 230 / 240 V) 60 °C 140 A
Rated operational current dc-5 (ie)
(110 V) 2 Poles in Series, 40 °C 160 A
(220 V) 3 Poles in Series, 40 °C 160 A
Rated operational power ac-3e (pe)
(415 V) 75 kW
(440 V) 90 kW
(500 V) 90 kW
(690 V) 75 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 37 kW
Ul certificate
20120925-E36588
Ul listing card
UL_E36588
Environment
Ccs certificate
GB14T00030
Coil consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 4 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 4 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 150 W
Coil operating limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 1x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 1 x 1 .... 4 mm²
Conventional free-air thermal current (ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A
Customs tariff number
85364900
EAC certificate
9AKK107046A8618
Rina certificate
ELE060313XG_002
Declaration of conformity - ccc
2020980304001304
Environmental product declaration - epd
1SFC100092D0201
ETIM - 8
EC000066 - Power contactor, AC switching
Etim 6
EC000066 - Power contactor, AC switching
Rmrs certificate
9AKK107045A6978
Short-circuit protective devices
gG Type Fuses 315 A
Circular design principles recyclability rate
Design for Closing Resource Loops - Standard EN45555 - 87.8 %
Declaration of conformity - ukca
2CMT2020-006118
Etim 7
EC000066 - Power contactor, AC switching
General use rating ul/csa
(600 V AC) 200 A
Dnv certificate
DNV_E-14043
Lr certificate
LR_14_70011(E1)
E-number (finland)
3706189
Improved resource efficiency for customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line - Achieved
Number of auxiliary contacts nc
1
Rohs information
2CMT2021-006277
Maximum electrical switching frequency
(AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Unspsc
39121529
E-number (norway)
4117621
Group waste to landfill target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility - Achieved
Rated breaking capacity ac-3
8 x Ie AC-3