Complementary
Ambient air temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Declaration of conformity - ce
2CMT2015-005436
Package level 1 gross weight
2 kg
Product net weight
1.8
kg
Cad dimensional drawing
2CDC001079B0201
Etim 4
EC001079 - Capacitor magnet contactor
Etim 5
EC001079 - Capacitor magnet contactor
Package level 1 height
162 mm
Product net width
90
mm
[ics] rated service breaking capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A
Cb certificate
SE-72472
Package level 1 units
box 1 piece
Package level 1 width
130 mm
Connecting capacity main circuit
Bar 30 mm²
Flexible with Cable End 2 x 6 ... 35 mm²
Rigid 1 x 10 ... 95 mm²
Cqc certificate
CQC2003010304088242
CQC2009010304353513
Environmental information
1SFC101001D0201
Idea granular category code (igcc)
4756 >> Capacitor magnet contactor
Instructions and manuals
5309660-60
Maximum operating altitude permissible
Without Derating 3000 m
Maximum operating voltage ul/csa
Main Circuit 600 V
Minimum order quantity
1 piece
Maximum mechanical switching frequency
3600 cycles per hour
mechanical durability
10 million
Number of main contacts no
3
Object classification code
Q
Package level 1 ean
7320500144572
Product net height
148
mm
Rated operational power ac-6b (pe)
(230 / 240 V) 40 °C, 50 / 60 Hz 35 kvar
(230 / 240 V) 55 °C, 50 / 60 Hz 35 kvar
(230 / 240 V) 70 °C, 50 / 60 Hz 30 kvar
(400 / 415 V) 40 °C, 50 / 60 Hz 65 kvar
(400 / 415 V) 70 °C, 50 / 60 Hz 55 kvar
(400 / 415 V) 55 °C, 50 / 60 Hz 65 kvar
(440 V) 40 °C, 50 / 60 Hz 65 kvar
(440 V) 55 °C, 50 / 60 Hz 65 kvar
(440 V) 70 °C, 50 / 60 Hz 55 kvar
(500 / 550 V), 40 °C, 50 / 60 Hz 70 kvar
(500 / 550 V) 55 °C, 50 / 60 Hz 70 kvar
(500 / 550 V) 70 °C, 50 / 60 Hz 60 kvar
(690 V) 40 °C, 50 / 60 Hz 80 kvar
(690 V) 55 °C, 50 / 60 Hz 80 kvar
(690 V) 70 °C, 50 / 60 Hz 70 kvar
Rated control circuit voltage (uc)
50 Hz 220 ... 230 V
60 Hz 230 ... 240 V
Rated short-time withstand current low voltage (icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 800 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 350 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1320 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 500 A
Rated frequency (f)
Main Circuit 50 / 60 Hz
Rated impulse withstand voltage (uimp)
Main Circuit 8 kV
Rated insulation voltage (ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Operate time
Between Coil De-energization and NC Contact Closing 7 ... 15 ms
Between Coil Energization and NO Contact Closing 10 ... 25 ms
Rated operational power ac-3 (pe)
(380 / 400 V) 45 kW
Rated operational voltage
Main Circuit 1000 V
Reach declaration
2CMT2021-006202
Resistance to shock acc
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 15 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 15 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 20 g
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 20 g
Environment
Coil consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 22 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 26 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 450 V·A
Coil operating limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting capacity auxiliary circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 1 x 1 .... 4 mm²
Connecting terminals (delivered in open position) main poles
M8 hexagon socket screw with single connector
Conventional free-air thermal current (ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 145 A
Customs tariff number
85364900
Culus certificate
20160916- E36588
Declaration of conformity - ccc
2020980304001551
2020980304001055
ETIM - 8
EC001079 - Capacitor contactor
Etim 6
EC001079 - Capacitor contactor
Declaration of conformity - ukca
2CMT2020-006118
Etim 7
EC001079 - Capacitor contactor
Rohs information
2CMT2021-006277
Maximum electrical switching frequency
240 cycles per hour
Unspsc
39121529