Additional Information
Data sheet, technical information
1SDC210100D0206
1SDC210099D0206
Eclass
V11.1 : 27370409
Package level 1 depth / length
285 mm
EAN
8056221006316
Product net depth / length
103.5
mm
Rohs status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Weee category
5. Small Equipment (No External Dimension More Than 50 cm)
Main
Product Name
Moulded Case Circuit Breaker
Product type
Breaking Part
version
F
Complementary
Declaration of conformity - ce
9AKK107680A2824
Package level 1 gross weight
3.8 kg
Product net weight
3.425
kg
Conflict minerals reporting template (cmrt)
9AKK108467A5658
Package level 1 height
240 mm
Product net width
140
mm
[ics] rated service breaking capacity
(220 V AC) 85 kA
(230 V AC) 85 kA
(240 V AC) 85 kA
(380 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 30 kA
(525 V AC) 30 kA
(690 V AC) 25 kA
(250 V DC) 2 Poles in Series 35 kA
(500 V DC) 2 Poles in Series 35 kA
Package level 1 units
box 1 piece
Package level 1 width
248 mm
Environmental information
9AKK107991A8215
9AKK108467A6707
Instructions and manuals
1SDH002011A1001
Order multiple
1 piece
Minimum order quantity
1 piece
Product main type
SACE Tmax XT
mechanical durability
240 cycles per hour
20000 cycle
Object classification code
Q
electrical durability
120 cycles per hour
5000 cycle
Package level 1 ean
8056221006316
Product net height
205
mm
Rated short-time withstand current low voltage (icw)
6 kA
Rated uninterrupted current (iu)
630 A
Rated impulse withstand voltage (uimp)
8 kV
Rated insulation voltage (ui)
1000 V
Short-circuit performance level
S
Rated operational voltage
690 V AC
750 V DC
Reach declaration
9AKK108466A1425
Sub-type
XT5
Poles description
3
Terminal connection type
Front
Rated ultimate short-circuit breaking capacity (icu)
(220 V AC) 85 kA
(230 V AC) 85 kA
(240 V AC) 85 kA
(380 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 30 kA
(525 V AC) 30 kA
(690 V AC) 25 kA
(250 V DC) 2 Poles in Series 35 kA
(500 V DC) 2 Poles in Series 35 kA
Environment
Customs tariff number
85389099
ETIM - 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Etim 6
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
standards
IEC
Etim 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Scip
a2a2fb3b-5a04-4d69-b154-0dce2dbe5175 Italy (IT)
E-number (finland)
3641402
Rohs information
9AKK108466A1424
Toxic substances control act - tsca
9AKK108467A8326